UPS output specifications

Nominal output voltage
Output voltage variation
(standard)
Output voltage variation
(reduced)
Output receptacles on
standalone UPSs—12kVA
models
Output receptacles on
standalone UPSs—8kVA
Short circuit capability
(Battery Mode)
Short circuit capability
(Normal Mode)
Nominal output frequency
Output frequency variation
Output overload
Voltage waveform
Full output

Environmental specifications

Feature
Operating
temperature
Storage temperature
Transit temperature
3 Phase UPS NA
120/208 Vac three-phase
108-132 Vac phase to neutral
187-229 Vac phase to phase
108-132 Vac phase to neutral
187-229 Vac phase to phase
Output module (2x L15-30R)
1x L15-30R
84 A, <300 ms
Limited by 50 A input breaker (30 A
source on 8kVA models)
50-60 Hz auto-detection (Normal
Mode)
50 or 60 Hz (Battery Mode)
Synchronized (Normal Mode)
±0.1 when not synchronized with
source (Battery Mode)
100-110%: load transfers to
Auto-Bypass Mode after 10 minutes
110-125%: load transfers to
Auto-Bypass Mode after 1 minute
125-150%: load transfers to
Auto-Bypass Mode after 5 seconds
>150%: load transfers to Auto-Bypass
Mode after 300 ms
Normal Mode and Battery Mode:
Sine wave; <2% THD with linear load;
<5% with nonlinear load
Three-phase
Specification
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 5°C to 25°C (41°F to
77°F)
0°C to 25°C (32°F to 77°F)
-25°C to 55°C (-13°F to 131°F)
3 Phase UPS INTL
230/400 Vac three-phase
187-255 Vac phase to neutral
324-441 Vac phase to phase
207-253 Vac phase to neutral
358-438 Vac phase to phase
Output module (2x IEC 309-16 A, 5
wire)
1x IEC 309-16 A, 5 wire
44 A, <300 ms
Limited by 30 A input breaker (16 A
source on 8kVA models)
50-60 Hz auto-detection (Normal
Mode)
50 or 60 Hz (Battery Mode)
Synchronized (Normal Mode)
±0.1 when not synchronized with
source (Battery Mode)
100-110%: load transfers to
Auto-Bypass Mode after 10 minutes
110-125%: load transfers to
Auto-Bypass Mode after 1 minute
125-150%: load transfers to
Auto-Bypass Mode after 5 seconds
>150%: load transfers to Auto-Bypass
Mode after 300 ms
Normal Mode and Battery Mode:
Sine wave; <2% THD with linear load;
<5% with nonlinear load
Three-phase
Specifications 103