Control Terminals; Relay Output Contacts - HP R1500 - UPS XR User Manual

Hp 3 phase ups user guide
Table of Contents

Advertisement

Pin number Signal name Function
4
5
6
7
8
9

Control terminals

The cables should be connected to the control terminal with a mating connector. Input and output terminals
have a functional isolation from terminal to terminal. They are connected to the UPS chassis through
individual 1 MW resistors.
If using a semiconductor switch type, pay attention to the proper polarity. A relay or other mechanical control
is preferred.

Relay output contacts

WARNING:
Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of
30 VAC/1 A and 60 Vdc/2 A nominal values.
No connection
GND
Signal common (tied to chassis)
No connection
No connection
No connection
No connection
The relay output contacts must not be connected to any utility connected circuits.
Direction from the UPS
Communication 76