HP R1500 - UPS XR User Manual page 53

Hp 3 phase ups user guide
Table of Contents

Advertisement

CAUTION:
drawn by this type of printer can overload the UPS.
Before connecting devices, verify that the UPS will not overload by checking that the ratings of the devices do
not exceed the UPS capacity. If the equipment rating is listed in amps, multiply the number of amps by the
nominal AC source to determine the VA.
To provide additional receptacles:
For the 8kVA models—Plug a PDU into the UPS output receptacle at the end of the power cord.
For the 12kVA models—
Install the included output module on the rear rack frame.
a.
Plug the output module into the special UPS output receptacle, located on the rear of the UPS.
b.
Item
1
2
3
4
5
6
Charging the UPS batteries
With the UPS in Standby mode, allow the batteries to charge before putting the UPS into service.
IMPORTANT:
devices. The batteries charge to:
Powering up the parallel system
Do not plug laser printers into the UPS output receptacles. The instantaneous current
Description
Rack corner post
Mounting locations
Mounting top bracket
Output cord
Mounting bottom bracket
Input cord
Charge the batteries for at least 48 hours before supplying backup power to
80 percent of their capacity within 5 hours
100 percent of their capacity within 48 hours
UPS installation 53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3 phase series

Table of Contents