Battery Specifications; Battery Runtimes - HP R1500 - UPS XR User Manual

Hp 3 phase ups user guide
Table of Contents

Advertisement

Feature
Relative humidity
Operating altitude
Transit altitude
Heat dissipation
Audible noise
Leakage current
Surge suppression
Safety conformance
Agency Markings
EMC (Class A)

Battery specifications

Feature
Configuration
Type
Monitoring
Charging

Battery runtimes

Battery runtimes are approximate and vary depending on the load configuration and battery charge.
Specification
Operating: 5% to 95%; noncondensing
Non-operating: 5% to 95%; 38.7°C (101.7°F)
maximum wet bulb temperature with no cosmetic
damage
Up to 1,000 m (3,300 ft) above sea level
Up to 2,000 m (6,600 ft) with 1% derating per + 100 m
(330 ft)
UP to 15,000 m (49,000 ft) above sea level
1432 BTU/hr maximum at 100% rated load (High
Efficiency Mode)
4094 BTU/hr maximum at 100% rated load (Standard
Mode)
Less than 58 dBA at 1 meter typical (Normal Mode)
Less than 64 dBA at 1 meter typical (Battery Mode)
<3.5 mA
ANSI C62.41 Category B3
3 Phase UPS NA: UL 1778 4th edition; CSA C22.2,
No. 107.1 and No. 107.3
3 Phase UPS INTL: EN 60950-1 and IEC 62040-1-1
3 Phase UPS NA: UL/cUL
3 Phase UPS INTL: CB, CE, GS, Ctick, GOST, BSMI
3 Phase UPS NA: FCC Part 15, ICES
3 Phase UPS INTL: EN 62040-2
Specification
UPS internal batteries: (40) 12 V, 5 Ah
+1 ERM: (20) 12 V, 9 Ah
+2 ERMs: (40) 12 V, 9 Ah
+3 ERMs: (60) 12 V, 9 Ah
+4 ERMs: (80) 12 V, 9 Ah
Each model contains maintenance-free, sealed,
valve-regulated lead-acid batteries.
Advanced monitoring for earlier failure detection and
warning
8-10 times the discharge time. Complete charge takes no
more than 48 hours. Approximately 5 hours to 80 percent
capacity at default nominal utility voltage and no load.
Specifications 104