Cord model number
12kVA Parallel NA
12kVA INTL
8kVA INTL
12kVA Parallel INTL
Power Bus Bar and Wireway specifications
Dimensions (WxDxH)
Weight
UPS connections
Rack placement
HP 10642 G2 Rack specifications
U height
Width
600 mm
42U
(23.8 in)
UPS input specifications
Nominal voltage
Nominal frequency
Frequency range
Default frequency
Rated input current—12kVA
models
Rated input current—8kVA
models
Connections—12kVA models IEC 309-60 A power cord
Connections—8kVA models
Connections—Parallel models Single Anderson input/output cord
Noise filtering
Input power factor
Input mode
Description
12 kW UL parallel
12 kW CE input
12 kW CE input/output IEC 309-16 A
12 kW CE parallel
Power Bus Bar
14.0 x 11.3 x 182.7 cm (5.5 x 4.4 x 71.9 in)
19 kg (42 lb)
6 power connections available
Installed to the rack rear vertical rail
(pre-installed)
Depth
Weight (without
side panels)
1,000 mm
115 kg (253 lb)
(39.4 in)
3 Phase UPS NA
120/208 V three-phase
50/60 Hz
45-65 Hz
Auto-detected
36 A
24 A
L21-30P power cord
connects to the Power Bus Bar
MOVs and common mode line filter
High efficiency setting: load
dependent
Standard setting: >0.99
Three-phase
Input plug type
Anderson
IEC 309-32 A
Anderson
Wireway
20 kg (45 lb)
Fits into the bottom 6U of standard
rack space (pre-installed)
Dynamic load (gross)
907.2 kg (2,000 lb)
3 Phase UPS INTL
230/400 V three-phase
50/60 Hz
45-65 Hz
Auto-detected
24 A
16 A
IEC 309-32 A power cord
IEC 309-16 A power cord
Single Anderson input/output cord
connects to the Power Bus Bar
MOVs and common mode line filter
High efficiency setting: load dependent
Standard setting: >0.99
Three-phase
Length
0.5 m (1.5 ft)
3.7 m (12 ft)
3.7/1.2 m (12/4 ft)
0.5 m (1.5 ft)
Static load
907.2 kg (2,000
lb)
Specifications 102