Connection Instructions and Diagrams 8/10 kVA

5.1

Battery Connections

The following illustration shows the wiring connections between the UPS and the Battery
Unit.
5.2

8/10 kVA Illustration

The following diagram shows the rear view of an 8/10 kVA UPS and a battery cabinet.
NOTE: Use only compatible cabinets! See page 6.
1600XP 8/10 kVA UPS
5.3

Connection Procedure

1) Ensure all power is locked and tagged out.
2) Remove the battery connector cover mounted on the UPS back panel.
3) Plug the DC Connectors of the Battery unit into the DC Connector socket on the
UPS unit (see section 3.0 UPS Power Connections).
5.4

Charger Connection

Battery cabinet model UH31-BC-1825 requires a 240 Vac connection between the UPS
and battery cabinet for battery charging. This connection is made from CN14A of the
battery cabinet to CN14 of the UPS (and CN14A of battery cabinet 2 to CN24 of battery
cabinet 1 if paralleling cabinets). NOTE: Without this connection the battery cabinet
will not be able to charge its batteries.
1600XP 8-22kVA Battery Cabinet Installation and Operation Manual
DANGER
Contacts are not rated with interrupting capacity.
Ensure the MCCB switch on the rear panel of the Battery Unit is set to the
OFF position before connecting the UPS to the battery cabinet.
BATTERY CABINET
9