Connection Instructions And Diagrams 14/18/22 Kva; Battery Connections; 14/18/22 Kva Illustration; Connection Procedure - Toshiba 1600XP SERIES Installation And Operation Manual

8-22kva battery cabinet
Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

4.0

Connection Instructions and Diagrams 14/18/22 kVA

4.1

Battery Connections

The following illustration shows the wiring connections between the UPS and the battery
cabinet.
4.2

14/18/22 kVA Illustration

The following diagram shows the rear view of a 14/18/22 kVA UPS and an 18 kVA battery
cabinet. NOTE: Use only compatible cabinets! See page 6.
1600XP 14/18/22 kVA UPS
4.3

Connection Procedure

1) Ensure all power is locked and tagged out.
2) Remove the battery connector cover mounted on the UPS back panel.
3) Plug the DC Connectors of the battery cabinet into the DC Connector socket on the
UPS unit (see section 3.0 UPS Power Connections).
4.4

Charger Connection

The UPS internal multi-tap transformer provides 240Vac to the UH31-BC-1825 Battery
Cabinet battery charging circuit. This connection is made from CN14A of the battery
cabinet to CN14 of the UPS (and CN14A of battery cabinet 2 to CN24 of battery cabinet 1 if
paralleling two cabinets). NOTE: Without this connection, the battery cabinet will not
be able to charge its batteries.
8
DANGER
Contacts are not rated with interrupting capacity.
Ensure the MCCB switch on the rear panel of the Battery Unit is set to the
OFF position before connecting the UPS to the battery cabinet.
1600XP 8-22kVA Battery Cabinet Installation and Operation Manual
BATTERY CABINET

Advertisement

Table of Contents
loading