Eaton Powerware 9170+ UPS 3–18 kVA User Manual page 55

Powerware series 3–18 kva
Table of Contents

Advertisement

The following notes are referenced in the system wiring diagrams
(Figure 32 through Figure 34).
NOTE 1
The customer must provide input overcurrent protection.
Section 240-21 or local requirements. See Table 6 on page 40 for circuit breaker ratings to
size the protection device according to local code requirements.
NOTE 2
The customer must size the AC circuit conductors.
conductors, including the neutral conductor, must be the same size (ampacity), have the same
rating (75°C) copper wire, and be sized according to the input circuit breaker. See Table 7 on
page 41 for recommended wire sizes. The UPS input and output conductors must be run
through separate conduits.
NOTE 3
The customer must provide output overcurrent protection.
Section 240-21 or local requirements. See Table 16 and Table 17 on pages 98 and 101 for
maximum output overcurrent protection device ratings.
NOTE 4 See "Equipment Clearances" on page 9 for installation and service clearances
before installing the UPS. Use flexible conduit on the UPS or the external battery cabinet if
either must be moved.
NOTE 5 External UPS battery cabinets are optional. See "Battery Cabinet Installation" on
page 61 for installation instructions.
NOTE 6 UPS output circuits shall be installed in dedicated conduit systems and not shared
with other electrical circuits.
+
Eaton 9170
UPS (3–18 kVA) User's Guide
UPS ELECTRICAL INSTALLATION
S
164201393 Rev E www.eaton.com/powerquality
See NEC
All AC circuit
See NEC
49