SPECIFICATIONS
Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued)
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Optional
UPS
Chargers
kVA/Watts
0
12/10000
1
12/10000
2
12/10000
3
12/10000
0
15/12500
1
15/12500
2
15/12500
0
18/15000
1
18/15000
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.
100
+
Eaton 9170
UPS (3–18 kVA) User's Guide
Nine- and Twelve-Slot Cabinet
Input Current
(200V)
(100/200V, 110/220V, 120/240V)
64A
80A
96A
102A**
80A
96A
102A**
96A
102A**
S
164201393 Rev E www.eaton.com/powerquality
Output Current
60A, 56A, 50A
60A, 56A, 50A
60A, 56A, 50A
60A, 56A, 50A
75A, 70A, 62.5A
75A, 70A, 62.5A
75A, 70A, 62.5A
90A, 84A, 75A
90A, 84A, 75A
Recommended
Heat
Input Service
Dissipation
80A
1145W
(3.90 kBTU/hr)
100A
1430W
(4.88 kBTU/hr)
125A
1720W
(5.85 kBTU/hr)
125A
1995W
(6.75 kBTU/hr)
100A
1430W
(4.88 kBTU/hr)
125A
1720W
(5.85 kBTU/hr)
125A
1995W
(6.75 kBTU/hr)
125A
1720W
(5.85 kBTU/hr)
125A
1995W
(6.75 kBTU/hr)