Eaton Powerware 9170+ UPS 3–18 kVA User Manual page 108

Powerware series 3–18 kva
Table of Contents

Advertisement

SPECIFICATIONS
Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674) (continued)
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Optional
UPS
Chargers
kVA/Watts
2
3/2100
3
3/2100
4
3/2100
5
3/2100
0
6/4200
1
6/4200
2
6/4200
3
6/4200
4
6/4200
5
6/4200
0
9/6300
1
9/6300
2
9/6300
3
9/6300
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.
102
+
Eaton 9170
UPS (3–18 kVA) User's Guide
Nine- and Twelve-Slot Cabinet
Input Current for
200/208/220/230/240V
46/45.5/45/44.5/44A
62/61.5/61/60.5/60A
78/77.5/77/76.5/76A
94/93.5/93/92.5/92A
28/27/26/25/24A
44/43/42/41/40A
60/59/58/57/56A
76/75/74/73/72A
92/91/90/89/88A
102A**
42/40.5/39/37.5/36A
58/56.5/55/53.5/52A
74/72.5/71/69.5/68A
90/88.5/87/85.5/84A
S
164201393 Rev E www.eaton.com/powerquality
Output Current for
Recommended
200/208/220/230/240V
15/14.5/14/13/12.5A
15/14.5/14/13/12.5A
15/14.5/14/13/12.5A
15/14.5/14/13/12.5A
30/29/28/26/25A
30/29/28/26/25A
30/29/28/26/25A
30/29/28/26/25A
30/29/28/26/25A
30/29/28/26/25A
45/43.5/42/39/37.5A
45/43.5/42/39/37.5A
45/43.5/42/39/37.5A
45/43.5/42/39/37.5A
Heat
Input Service
Dissipation
60A
860W
(2.93 kBTU/hr)
80A
1145W
(3.90 kBTU/hr)
100A
1430W
(4.88 kBTU/hr)
125A
1720W
(5.85 kBTU/hr)
40A
570W
(1.95 kBTU/hr)
60A
860W
(2.93 kBTU/hr)
80A
1145W
(3.90 kBTU/hr)
100A
1430W
(4.88 kBTU/hr)
125A
1720W
(5.85 kBTU/hr)
125A
1995W
(6.75 kBTU/hr)
60A
860W
(2.93 kBTU/hr)
80A
1145W
(3.90 kBTU/hr)
100A
1430W
(4.88 kBTU/hr)
125A
1720W
(5.85 kBTU/hr)