Siemens Synova FC330A Operating Manual page 41

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

Functional test of manual call points
Response
indicator
Test−
key
Response
indicator
Button
Fire & Security Products
Siemens Building Technologies Group
Test procedure for type KAC
1. Set the desired zone into detector test mode (+ page 34).
2. Insert the test key into the opening at the lower left side of the housing.
A test alarm is simulated.
Ü
3. Observe, whether the response indicator near the upper right corner of the housing flashes.
4. Remove the test key.
The functional testing is completed.
Ü
If the tested manual call point did not respond, call the SIEMENS service organization.
"
Test procedure for type DIN (indirect activation)
1. Set the desired zone into detector test mode (+ page 34).
2. Open the housing of the manual call point with the key.
3. Press down the button completely.
A test alarm is simulated.
Ü
4. Observe, whether the response indicator, a red LED to the right of the button, flashes.
5. Close the housing.
The functional testing is completed.
Ü
If the tested manual call point did not respond, call the SIEMENS service organization.
"
Control console
Display shows
Ü
Each test alarm is indicated in the display for a few seconds and also registered in the event
"
memory.
mode 'detector TEST' ACTIVE
*
> test−ALARM zone ###/##
WED 21.7.99
15:00
37
e1973c-8
02.2004