Siemens Synova FC330A Operating Manual page 21

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

V1 =
min.
V2 =
min.
Fire & Security Products
Siemens Building Technologies Group
Alarm acknowledgement time V1
The alarm acknowledgement time is active for automatic detectors when the system opera-
n
tes in "manned" mode.
The system checks whether someone acknowledges the alarm message within this prepro-
n
grammed time.
An alarm must be acknowledged before V1 expires, otherwise the alarm is transmitted to the
n
fire department.
The remaining time is indicated on the text dis-
n
play in minutes and seconds.
Alarm investigation time V2
The alarm investigation time is active for automatic detectors when the system operates in
n
"manned" mode.
It limits the time for investigating the fire location to an preprogrammed length.
n
On expiration of this time the alarm is transmitted to the fire department.
n
In case of minor incidents, an alarm must be reset before V2 expires.
n
The remaining time is indicated on the text dis-
n
play in minutes and seconds.
ALARM zone ###/## / ######
ALARM zone ###/## / ######
1:27 min
1 ( 1)
2:27 min
1 ( 1)
17
e1973c-3
02.2004