Faults - Siemens Synova FC330A Operating Manual

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

Faults

How do I respond to fault messages?
What remedies are available to the user?
Emergency power
supply:
32
Fire & Security Products
Siemens Building Technologies Group
Fault messages are issued on the text display if a malfunction in the system, the cabling or the
attached devices is detected. Additionally the LED in the fault display field is blinking.
1. Confirm the message by pressing the Acknowledge key.
The yellow LED in the fault display field changes from blinking to constant on.
Ü
2. Read the fault message on the display and decide, whether the fault can be remedied by the
user (see next paragraph: What remedies are available to the user).
3. To cancel the fault message after the fault is remedied, press the Reset key.
WARNING
If the fault cannot remedied by the user, immediately call the SIEMENS service organiza-
tion!
Only a few faults can be remedied by the user. These are listed below. For all other faults call the
SIEMENS service organization.
Defective or missing detector
Display shows
Ü
or
Display shows
Ü
Broken glass on manual call point
Display shows
Ü
Manual call point with broken glass is
Ü
flashing
If a detector is missing, insert a detector of
"
the same type into the detector base.
If a detector is damaged, replace it with a detector of the same type and order a new reserve
"
detector from the SIEMENS service organization.
If a manual call point has been operated and the glass is broken, replace it, then press the key
"
Reset
.
Mains POWER OFF
Display shows
Ü
If the public power supply is down, no action is required. The emergency battery supplies the
n
system for several hours (according to local requirements at least 12 h, max. 72 h), depen-
h
ding on the size of the emergency battery.
If the outage is not in the public power supply:
n
1. Check the power fuse at the main distribution panel of the building.
2. If the fuse is blown, replace the fuse.
Printer out of paper
Insert a new paper roll (+ page 45, Printer: Paper replenishing).
"
FAULT message(s):
zone ### elem. ##: dev. DEFECTIVE
*
TUE 27.7.99
10:35
FAULT message(s):
*
zone ### elem. ##: NO RESPONSE
TUE 27.7.99
10:35
FAULT message(s):
*
zone ### elem ##: Broken glass
TUE 27.7.99
10:35
FAULT message(s):
EARTH FAULT to 24V
*
TUE 27.7.99
10:35
total:###
total:###
total:###
total:###
e1973c-7