Zone isolation procedure
Permanent disabling
Disabling for a few
hours
Permanent disabling
Disabling for a few
hours
Fire & Security Products
Siemens Building Technologies Group
1. Press
.
St
Display shows
Ü
2. Select option 2. ä 1. ä 1.
Display shows
Ü
Now you can disable single zones, a range of
detector zones or all zones as described be-
low:
Disable single zones
1. Enter the desired zone number (e. g.
2).
Display shows
Ü
2. Press
to disable the single zone.
ok
Display shows
Ü
3. Enter 99 for permanent disabling.
Display shows
Ü
or
Enter the desired disabling time in full
"
hours (e. g. 2).
Display shows
Ü
4. Press
to finish the zone disabling
St
procedure.
or
Enter another single zone number to disable.
"
Display shows
Ü
The yellow LED isolation is on.
Ü
Disable a range of zones
1. Enter the first zone number of the
range of zones to be disabled (e. g. 2).
Display shows
Ü
2. Enter the last zone number of the range
of zones to be disabled (e. g. 5).
Display shows
Ü
3. Enter 99 for permanent disabling.
Display shows
Ü
or
Enter the desired disabling time in full
"
hours (e. g. 2).
Display shows
Ü
4. Press
to finish the zone disabling
St
procedure.
or
Enter another zone number to disable.
"
Display shows
Ü
The yellow LED isolation is on.
Ü
SELECT:
1. ENabling
(main menu)
2. DISabling
*
3. INFO polling
4. other functions
DISable zones:
(range ### to ###)
*
> zone no.?
(555 = all)
hm: back to menu
zone ### SELECTED.
> 2nd zone no.? (range ### − ###)
*
hm: back to menu
zone ### SELECTED
*
> hours DISABLED?
zone ### permanent DISABLED
(hm = end)
new zone no.?
*
hm: back to menu
zone ### DISABLED for ## hours
(hm = end)
new zone no.?
*
hm: back to menu
parts of system DISABLED
*
WED 21.7.00
15:00
zone ### SELECTED.
> 2nd zone no.? (range ### − ###)
*
hm: back to menu
zone ### − ### SELECTED
> hours DISABLED?
*
hm: back to menu
zones ### − ### permanent DISABLED
*
(hm = end)
new zone no.?
hm: back to menu
zones ### − ### DISABLED for ## hours
(hm = end)
new zone no.?
*
hm: back to menu
parts of system DISABLED
*
WED 21.7.00
15:00
Stop: end operating
ok = SINGLE zone
Stop: end operating
(99=permanent)
Stop: end operating
Stop: end operating
total:###
ok = SINGLE zone
_
Stop: end operating
(99=permanent)
Stop: end operating
Stop: end operating
Stop: end operating