Synova® FC330A
Fire detection system
Operating manual
System operation for user
Phase 4
Fire & Security Products
Siemens Building Technologies Group

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Synova FC330A

  • Page 1 Synova® FC330A Fire detection system Operating manual System operation for user Phase 4 Fire & Security Products Siemens Building Technologies Group...
  • Page 2 Data and design subject to change without notice. / Supply subject to availability E Copyright by Siemens Building Technologies AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche...
  • Page 3: Table Of Contents

    ............06.2003 Fire & Security Products Siemens Building Technologies Group...
  • Page 4 06.2003 Fire & Security Products Siemens Building Technologies Group...
  • Page 5: Introduction

    Introduction Fire & Security Products e1973c-1 Siemens Building Technologies Group 02.2004...
  • Page 6: About This Operation Manual

    The result of an action is marked with an arrow. Ü In body text you will find quotations like display texts, keys or LED−fields or LEDS. Frequently used keys are shown as they look like on the console, e.g. Fire & Security Products e1973c-1 Siemens Building Technologies Group 02.2004...
  • Page 7: Fundamentals

    Fundamentals Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 8: Control Console Layout

    Returns to the previous menu. Delete key Deletes the character left of the cursor. Ò Keylock switch Gives access to user operating level 2 without password. Only when keylock switch is installed. Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 9: Floor Panel

    Gives access to user operating level 2 without password. The display of the floor panel indicates the same event text as shown at the control console. It only displays one message at a time. Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 10: Overview Operating Menu

    4. user text ConTrol zone View parameter settings detector zones INFO: 1. configuration det. zones View parameter settings addr. lines (3.4) 2. configuration addr. lines View parameter settings LON-bus 3. configuration LON devices Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 11 4. user text ConTrol zone Print parameter settings detector zones PRINT: 1. configuration det. zones Print parameter settings addr. lines (4.3.4) 2. configuration addr. lines Print parameter settings LON-bus 3. configuration LON devices Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 12 ERASE data: 1. ERASE alarm counter (not locked) (4.4.4) 2. ERASE event memory only for specialized personell 3. ERASE conf + sys data to erase ’non−alarm’ events 4. ERASE element status Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 13: Fundamental Operation

    In this operation manual, selecting a menu item will be described from now on in a short form as follows: Select option 2. ä 1. ä 2. " DISABLE element: Display shows Ü > zone no.? (range ### − ###) hm: back to menu Stop: end operating Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 14: Normal Operation

    Reset Remote alarm Remote alarm Alarm delay Start/ System on Stop fault / off active Alarm horn Premises Fault fault / off manned Isolation System fault Detector test mode FC330A Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 15: Operating Access

    Ü Remote alarm Alarm delay Remote alarm Start/ System on active Stop fault / off Alarm horn Premises Fault fault / off manned Isolation System fault Detector test mode FC330A Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 16 3. Proceed operating (access is now provided) Log out There is no log out procedure, because the operating access expires automatically if no key is pressed within a certain time (+ page 11, Automatic timeout). Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 17: Operating "Manned" And "Unmanned

    Toggle between “manned” and “unmanned” via menu which is described next page. " Operating state ”unmanned” NORMAL OPERATION Display shows Ü WED 21.7.99 15:00 Operating state ”manned” NORMAL OPERATION Display shows Ü mode ’manned’ WED 21.7.99 15:00 Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 18 Display shows Ü hm: back to menu Stop: end operating Extra time max. 4. Enter the extra time. The time until the system is set to manned mode is displayed. Ü Fire & Security Products e1973c-2 Siemens Building Technologies Group 02.2004...
  • Page 19: Alarm

    Alarm Fire & Security Products e1973c-3 Siemens Building Technologies Group 02.2004...
  • Page 20: Cerberus Alarm Concept (Cac)

    V2 by pressing the Reset key. Ü The system is in the normal operation mode again. The times V1 and V2 are only relevant, when the remote transmission is installed. Fire & Security Products e1973c-3 Siemens Building Technologies Group 02.2004...
  • Page 21 In case of minor incidents, an alarm must be reset before V2 expires. The remaining time is indicated on the text dis- play in minutes and seconds. ALARM zone ###/## / ###### 2:27 min 1 ( 1) Fire & Security Products e1973c-3 Siemens Building Technologies Group 02.2004...
  • Page 22: Alarm

    Reset Remote alarm Alarm delay Remote alarm Start/ System on Stop fault / off active Alarm horn Premises Fault fault / off manned Isolation System fault Detector test mode FC330A Fire & Security Products e1973c-3 Siemens Building Technologies Group 02.2004...
  • Page 23 What to do after an alarm Reset system if normal conditions appeared. " If a manual call point was activated while the alarm, insert a new front glass in the actual call " point. Fire & Security Products e1973c-3 Siemens Building Technologies Group 02.2004...
  • Page 24 Fire & Security Products e1973c-3 Siemens Building Technologies Group 02.2004...
  • Page 25: Disable/Enable System Parts

    Disable/Enable System Parts Fire & Security Products e1973c-4 Siemens Building Technologies Group 02.2004...
  • Page 26: Temporary Isolation Of A Detector Zone

    WARNING A zone that has been isolated cannot trigger any danger or fault messages! As soon as conditions have returned to normal, isolated zones have immediately to be enabled again! Fire & Security Products e1973c-4 Siemens Building Technologies Group 02.2004...
  • Page 27 Enter another zone number to disable. " parts of system DISABLED total:### Display shows Ü The yellow LED isolation is on. Ü WED 21.7.00 15:00 Fire & Security Products e1973c-4 Siemens Building Technologies Group 02.2004...
  • Page 28 2. Select option 1. ä 1. ä 1. ENable zone: (range ### to ###) Display shows Ü > zone no.? (555 = all) The yellow LED isolation is off. Ü hm: back to menu Stop: end operating Fire & Security Products e1973c-4 Siemens Building Technologies Group 02.2004...
  • Page 29 Stop: end operating 3. Press to go back to the submenu. DISabling: 1. detector ’zone’ Display shows Ü (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’ Fire & Security Products e1973c-4 Siemens Building Technologies Group 02.2004...
  • Page 30: Temporary Isolation Of A Single Detector

    The yellow LED isolation is on. Ü hm: back to menu Stop: end operating 6. Press to finish the element disa- bling procedure or enter a new zone number to disable another single ele- ment. Fire & Security Products e1973c-4 Siemens Building Technologies Group 02.2004...
  • Page 31 (F1 /hm = enabling) next elem.? 5. Enter another element number to ena- 6. Press to enable the element before the timeout has expired. 7. Press to go back to the submenu. Fire & Security Products e1973c-4 Siemens Building Technologies Group 02.2004...
  • Page 32: Remote Transmission

    The remote fire alarm transmission is enabled. Ü The yellow LEDs of the display fields Isolation and Remote alarm/fault off are off, if no other Ü parts of the system are isolated. Fire & Security Products e1973c-5 Siemens Building Technologies Group 02.2004...
  • Page 33 Stop: end operating The remote fault transmission is enabled. Ü The yellow LED of the display filed Isolation is off, if no other parts of the system are isola- Ü ted. Fire & Security Products e1973c-5 Siemens Building Technologies Group 02.2004...
  • Page 34: Alarm Devices

    The desired alarm devices are enabled. Ü The yellow LEDs of the display fields Isolation and Alarm horn fault/off are off, if no other Ü parts of the system are isolated. Fire & Security Products e1973c-6 Siemens Building Technologies Group 02.2004...
  • Page 35: Faults

    Faults Fire & Security Products e1973c-7 Siemens Building Technologies Group 02.2004...
  • Page 36: Faults

    (see next paragraph: What remedies are available to the user). 3. To cancel the fault message after the fault is remedied, press the Reset key. WARNING If the fault cannot remedied by the user, immediately call the SIEMENS service organiza- tion! What remedies are available to the user? Only a few faults can be remedied by the user.
  • Page 37: Maintenance

    Maintenance Fire & Security Products e1973c-8 Siemens Building Technologies Group 02.2004...
  • Page 38: Detector Test

    Stop: end operating 3. Enter the desired zone numbers (e. g. 1 and 2; max. 4 zones). Use the to separate the numbers and the key to cancel keying errors. Fire & Security Products e1973c-8 Siemens Building Technologies Group 02.2004...
  • Page 39 3. Enter “0” (zero) and press Display shows Ü ’DET. TEST’ mode TERMINATED for a few seconds timeout /hm: menu Stop: end operating The detector test mode is terminated for Ü all detector zones. Fire & Security Products e1973c-8 Siemens Building Technologies Group 02.2004...
  • Page 40 Ü If the tested detector did not respond, check the gas can inside the detector tester RE6 or the " battery inside the tester DZ1193. If defective detectors are found call the SIEMENS service organization. Detector tester RE6 (gas) Test procedure for detector tester RE6T Heat detector 1.
  • Page 41 Test− The functional testing is completed. Ü If the tested manual call point did not respond, call the SIEMENS service organization. " Test procedure for type DIN (indirect activation) 1. Set the desired zone into detector test mode (+ page 34).
  • Page 42: Lamp Test

    − all LEDs on? − buzzer audible? − missing segments in text display? If one or more devices are malfunctional, call the SIEMENS service organization. Lamp test on local indication and control panels + page 5. Fire & Security Products...
  • Page 43: Battery Load Test

    Display shows Ü timeout /hm: menu Stop: end operating for a few seconds If the battery load test yields insufficent battery capacity, call the SIEMENS service organization to replace the battery. Fire & Security Products e1973c-10 Siemens Building Technologies Group...
  • Page 44: Test Of Acoustic Alarm Devices

    After the test has finished, the submenu is displayed again. Ü If an acoustic device did not respond in the test, call the SIEMENS service organization for repla- cement or repair. The horn test can be stopped before expiration of the 30 seconds by pressing "...
  • Page 45: Test Of Remote Transmission (Rt)

    After the test has finished, the submenu is displayed again. Ü If the remote alarm did not arrive at the fire departement, call the SIEMENS service organization for repair. The test can be stopped before expiration of the 30 seconds by pressing "...
  • Page 46 Fire & Security Products e1973c-12 Siemens Building Technologies Group 02.2004...
  • Page 47: Other Functions

    Other Functions Fire & Security Products e1973c-13 Siemens Building Technologies Group 02.2004...
  • Page 48: Printer Disabling/Enabling

    /hm: menu Stop: end operating The printer is enabled. Ü The yellow LED of the display field Isolation is off, if no other parts of the system are isola- Ü ted. Fire & Security Products e1973c-13 Siemens Building Technologies Group 02.2004...
  • Page 49: Paper Replacement With Logging Printer B2Q191

    279 977 (4 pieces) JUJU TP 50KS−A HOSHU PS 65 B1 MITSUBISHI F−200 U7X Print intensity If the print intensity is too low, call the SIEMENS service organization. Fire & Security Products e1973c-13 Siemens Building Technologies Group 02.2004...
  • Page 50: Poll Alarm Counter

    ### Display shows Ü remote alarms: ### for a few seconds timeout /hm: menu Stop: end operating The submenu is displayed. Ü 3. Use to terminate the alarm counter polling. Fire & Security Products e1973c-14 Siemens Building Technologies Group 02.2004...
  • Page 51: Poll Event Memory

    EVENT no ##: ##.##.## ##:##:## Display shows event text ... Ü : forward : backwards 4. Use to go back to the submenu or to terminate the event memory polling. Fire & Security Products e1973c-14 Siemens Building Technologies Group 02.2004...
  • Page 52: Poll User Text Of Zones Or Elements

    ###/ −: ###### Display shows Ü ground floor main entrance : forward : backwards 4. Use to go back to the submenu or to terminate the user text polling. Fire & Security Products e1973c-14 Siemens Building Technologies Group 02.2004...
  • Page 53: Poll System Status

    FAULT messages: total:## fault messages....Display shows Ü : forward : backwards 5. Use to go back to the submenu or to terminate the system status polling. Fire & Security Products e1973c-14 Siemens Building Technologies Group 02.2004...
  • Page 54: Poll Configuration Data

    ### name=###### type=###### Display shows al=###### incr=###### dr=###### Ü trouble=###### zn ### el ## 6. Use to go back to the submenu or to terminate the configuration data polling. Fire & Security Products e1973c-14 Siemens Building Technologies Group 02.2004...
  • Page 55: Printout

    Display shows Ü (4.3.4) 2. configuration addr. lines 3. configuration LON devices 3. Select the information to be printed. PRINTOUT in process: Display shows Ü hm: stop print Stop: end operating Fire & Security Products e1973c-15 Siemens Building Technologies Group 02.2004...
  • Page 56: Set Time And Date

    Time and date are set to the current va- Ü lues. FUNCTIONS: 1. switching alarm org. Display shows (4.1) 2. set time / date Ü 6. Use to terminate the time and date setting. Fire & Security Products e1973c-16 Siemens Building Technologies Group 02.2004...
  • Page 57 Fire & Security Products Back Siemens Building Technologies Group 02.2004...
  • Page 58 Siemens Building Technologies AG Alte Landstrasse 411 CH-8708 Männedorf Tel. +41 1 − 922 61 11 +41 1 − 922 64 50 www.cerberus.ch Fire & Security Products Back Document no. e1973c Manual FD-M Siemens Building Technologies Group 02.2004 Edition 02.2004...