Installation
Horizontal Terminations using 8" Diameter Vent
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.
20' (max)
15 feet
10 feet
5 feet
0 feet
NOTE:
• Horizontal sections require a 1/4" rise every 12"
of travel.
• The maximum vertical height is 20'.
• The maximum horizontal length is 25'.
• One horizontal elbow (45° or 90°) is allowed
when using 8" vent. The horizontal vent length is
calculated by adding the length before and after
the elbow (H1 + H2 = horizontal vent length).
Travis Industries
(for qualified installers only)
Restrictor
Position #7
NOTE:
Restrictor positions are based upon
lab tests. The ideal restrictor position
may vary slightly.
Restrictor
Position #1
6-5/8" to 8" dia. Adapter
(must be placed directly off the top of
the fireplace - Part # 925T)
4040708
H2
H1
Horizontal
Elbow
2 3
20' (max)
15 feet
10 feet
5 feet
0 feet
Vertical
Elbow
1 0 0 - 0 1 1 6 0