DESCRIPTION

The LonWorks driver allows the FieldServer to transfer data to and from devices using LonWorks protocol. The FieldServer
can emulate either a Server or Client. The FS-B2011 and FS-B30 Series FieldServers have a built-in LonWorks Interface. A
Fieldbus connection is available on the FieldServer. The FS-B30 can handle up to 4096 Network Variables and the FS-B2011
up to 1000 which can be of the Standard Network Variable Types (SNVT) and/or User-defined Network Variable Types
(UNVT).
2

DEFINITIONS

2.1

NV Updates/Polls

On LonWorks networks, information is transferred using Network Variable Updates and Network Variable Polls. The Client
requests Network Variables from the Server using Network Variable Polls and Network Variable Updates occur when a Client
sends Network Variables to a Server.
2.2

Network Management

The FieldServer is able to set its own Domain, Subnet and Node ID at start-up using the FieldServer configuration file.
Alternatively, the FieldServer is capable of being commissioned and bound by Network Management Tools such as
LonMaker® - see Appendix B.1.1 for further information.

2.2.1 LonWorks - Program ID Calculation (SPID)

Network management tools use the Program ID to identify the different applications running on each device. Two devices on
a network may have the same Program ID only if they have identical application/configurations
The Program ID for the FieldServer consists of a fixed and a variable field (XX in the Program ID below)..
90:00:95:47:1E:02:04:XX
The fixed part does not change for different configuration files or for different LonWorks driver versions. The variable part
XX, which is also defined as the Model or Revision number, does however change.
The variable part is calculated at start-up when the configuration is loaded on the FieldServer. Certain critical fields in the
configuration file are used to calculate this variable part of the Program ID. Thus if the configuration file changes significantly
(critical fields) the Program ID will change. Also, as we add new features and capabilities to the LonWorks driver, this variable
part of the Program ID may be different between LonWorks driver versions (even though the configuration file is the same).
It is possible though very unlikely that through a change in LonWorks driver and/or configuration file, the program IDs
calculates out identical to another combination of driver and configuration. If this is the case with two FieldServers on the
same network that run different configurations, one of these devices may fail to commission properly.
The following configuration can be used to force the SPID.
Connections
Adapter
, Protocol
Lonworks
, Lonworks