Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-74 Veeder-Root
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version:
1.01
Document Revision: 3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FS-8700-74 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for FieldServer FS-8700-74

  • Page 1 A Sierra Monitor Company Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-74 Veeder-Root APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after May 1, 2001 Driver Version: 1.01 Document Revision: 3...
  • Page 2: Table Of Contents

    Appendix C.8. Advanced Example 8 – Active Alarm Report ..........31 Appendix C.9. Advanced Example 9 – Cleared Alarm Report ..........32 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 3: Veeder-Root Driver Description

    FS-8700-74 Veeder Root Driver Manual Page 3 of 33 Veeder-Root Driver Description The Veeder-Root Serial Driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 ports using Veeder-Root protocol as defined in Veeder Root Document 576013-635 Revision J.
  • Page 4: Driver Scope Of Supply

    Driver Manual. 2.2. Provided by the Supplier of 3 Party Equipment 2.2.1. Required 3 Party Hardware PART # DESCRIPTION Veeder-Root Panel FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 5: Hardware Connections

    FS-8700-74 Veeder Root Driver Manual Page 5 of 33 Hardware Connections The FieldServer is connected to the Veeder-Root Panel as shown below. Configure the Veeder-Root Panel according to manufacturer’s instructions. TLS-350 8917-07 RJ45 CAT 5 Cable Connect to RS232 port P1-P8...
  • Page 6: Configuring The Fieldserver As A Veeder-Root Client

    This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Veeder-Root Device. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Veeder-Root Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays”...
  • Page 7: Client Side Connections

    Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 8: Client Side Nodes

    Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 9: Driver Specific Map Descriptor Parameters

    Legal Values Scan_Interval Rate at which data is polled >0.1s ¥ See Appendix A.1 for Data Type, Address and Length Limitations. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 10: Map Descriptor Example 1 - Alarms

    05 = Tank Low Product Alarm The driver sets array DA_T1 as follows Index=0 : Value=1 (Summary) Index=2 : Value=2 (Leak) Index=5 : Value=5 (Product) FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 11: Map Descriptor Example 2 - Inventory

    DA_INVENTORY starting at the this example. zero’th element (offset=0) and 10 elements of the array are reserved for this data. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 12: Map Descriptor Example 3 - Most Recent Delivery Report

    Starting Height Ending Height Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Scan_Interval node_name Address Length Data_Type DeliveryPoll01 DA_DELIVERY rdbc 1.0s Node_A In-Tank Delivery FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 13: Configuring The Fieldserver As A (Veeder-Root Driver) Server

    It may be possible to extend and document the server at the request of an end-user. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 14: Appendix A. Advanced Topics

    Start P-Line Leak Detect Test Stop P-Line Leak Detect Test Start WPLLD Leak Detect Test Stop WPLLD Leak Detect Test System Status FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 15: Appendix A.2. Supported Functions

    7 Stop Pressure Line Leak Test 10 Start WPLLD Line Leak Test (3.0 GPH only in V18) 10 Stop WPLLD Line Leak Test FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 16: Appendix A.3. Alarm Types

    2 Tank 24 Tank AccuChart Calibration Warning 2 Tank 25 Tank HRM Reconciliation Warning 2 Tank 26 Tank HRM Reconciliation Alarm FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 17 26 VLLD Periodic Test Fault Alarm 6 Volumetric Line Leak 27 VLLD Annual Test Fault Alarm 6 Volumetric Line Leak 28 VLLD Fuel Out Alarm FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 18 4 BIR Close Daily Warning 21 Pressure Line Leak 1 PLLD Setup Data Warning 21 Pressure Line Leak 2 PLLD Gross Test Fail Alarm FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 19 99 Externally Detected Alarm 12 Polling - Could Not Update Queue 99 Externally Detected Alarm 13 Polling - Invalid Data Type Requested FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 20: Appendix A.4. Security Codes

    If the security feature has been disabled on the panel the set the route to zero as illustrated in the following CSV file fragment. Nodes Node_Name, Port, Protocol, Route Node_A , P1 , VEEDER , 0 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 21: Appendix B. Trouble Shooting And Driver Error Messages

    (less then 5%). • Several errors in consecutive messages may cause the FieldServer kernel to place the node offline in which case polling is slowed significantly until good communications are re- established.
  • Page 22 You cannot take any corrective action to eliminate this error. VRoot:#12 Err. Command Report the message to FieldServer support. It will assist in the 0x54. Bad confirmation diagnosis of the error if you can take a port log. . There are a few code.
  • Page 23 #7 messages. If there are any correct the errors by editing the Rqd=%d CSV file. Then reset the FieldServer. If the driver is still producing error 16 then you should report this to FieldServer support. Provide a copy of your configuration file and a port log to assist in the diagnosis of this error.
  • Page 24: Appendix B.1. Driver Stats

    Additional information is provided in Appendix A.4 Appendix B.1. Driver Stats In addition to the standard FieldServer communication statistics described in the FieldServer User’s Manual Veeder-Root Driver can also expose some driver statistics by writing data to a Data Array. A special Map Descriptor named “vroot-stats” is required.
  • Page 25: Appendix B.2. Table Of Module Types

    25 - Serial Satellite Module 26 - Three Probe / Three Liquid Sensor Module 27 - Three PLLD Sensor Module FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 26: Appendix C. Advanced Map Descriptor Examples

    Type-A Sensor relying on the Type-B Sensor response to a different Universal Sensor poll. Press. Line WPLLD Relay FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 27: Appendix C.2. Advanced Example 2 - Resetting Remote Alarms

    DA_Byte_Name and the DA_Float_Name. Make sure that both of these arrays are UINT32 or FLOAT if you use them. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 28: Appendix C.4. Advanced Example 4 - System Diagnostics

    Prom test result Map_Descriptor_Name,, Data_Array_Name, Data_Array_Offset, Scan_interval, Function, node_name, Address, Length, Veed_Function, Data_Type System1poll_1 DA_SELF_TEST , 10.0s rdbc Node_A , 0x901 Misc. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 29: Appendix C.5. Advanced Example 5 - System Revision Level Report

    Data_Array_Name, Data_Array_Offset, Scan_interval, Function, node_name, Address, Length, Veed_Function, Data_Type System1poll_1 , DA_REVISION 10.0s rdbc Node_A , 100 , 0x902 Misc. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 30: Appendix C.6. Advanced Example 6 - System Revision Level Report Ii

    Data_Array_Offset, Scan_interval, Function, node_name, Address, Length, Veed_Function, Data_Type System1poll_1 , DA_REVISION2 , 10.0s rdbc Node_A , 100 , 0x905 Misc. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 31: Appendix C.7. Advanced Example 7 - Stick Height Report

    Map_Descriptors Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Scan_Interval, Function, node_name, Address, Length, Data_Type AlarmPoll-11 , DA_ACTIVEALM , 2.0s rdbc Node_A, Active Alarm Report FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 32: Appendix C.9. Advanced Example 9 - Cleared Alarm Report

    Thus if a 02 = Tank Leak Alarm was cleared then at index=2 the value stored will be a one. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...
  • Page 33 FS-8700-74 Veeder Root Driver Manual Page 33 of 33 This page intentionally left blank. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com...