Summary of Contents for FieldServer FS-8700-03 DF1
Page 1
A Sierra Monitor Company Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-03 DF1 APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after May 1, 2001 Driver Version: 1.01 Document Revision: 16...
Page 3 of 16 Allen Bradley DF1 Description The DF1 driver allows the FieldServer to transfer data to and from devices over RS-232 using DF1 protocol. The FieldServer can emulate either a Server or Client. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.
DF1 Client, e.g. Wonderware, Intellution FIX, GE Cimplicity, etc. If FieldServer used as Allen Bradley DF1 Client If FieldServer used as Allen Bradley DF1 Server FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com...
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FS).
Handshaking is not supported, only the enabling of the RTS/CTS lines FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com...
Scaling max in Connected Node_High_Scale* -32767 to 32767, 100 Node Not all PLC’s can support all File_Types. Refer to DFS for further information. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com...
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).
Scaling max in Connected Node_High_Scale* -32767 to 32767, 100 Node Not all PLC’s can support all File_Types. Refer to DFS for further information. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com...
Server map 1: N21: 0-31 Server map 2: N21: 32-100 This will panic the FieldServer and crash RS view as the DF1 will attempt to map N21: 0-100 If set up as: Server Map 1: N21: 0-100 No problems are experienced Appendix A.2.