6.2.4 Client Side Map Descriptor Example

// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Lon_Function , Function , Node_Name , SNVT_Type
TempOut1
, DA_FO_01
TempOut2
, DA_FO_01
TempOut3
, DA_FO_01
TempIn
, DA_FI_01
This field
determines the
Map
Descriptor's
Required for Throttling Mode: This field specifies the
function. See
minimum change needed for a Network Variable's
Section 6.1.2
value to invoke an NV Update.
for more
information.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, 0
, NVUOIMT
, Wrbc
, 1
, NVUOIMX
, Wrbc
, 2
, NVUOIMC
, Wrbc
, 0
, NVPIIMT
, Rdbc
Page 14 of 72
, Nv_Delta_Value , Min_Scan_Time , Max_Scan_Time , Scan_Interval
, LON_1
, SNVT_Temp_f , 10
, LON_1
, SNVT_Temp_f , -
, LON_1
, SNVT_Temp_f , -
, LON_1
, SNVT_Temp_f , -
The Data Array will be
sampled and evaluated for
delta change once every
Min_Scan_Time (seconds)
If found during Min_Scan_Time
sampling (Throttling Mode) that
Max_Scan_Time has elapsed since the
last NV Update, a new NV Update will
be transmitted.
, 5
, 20
, -
, -
, -
, -
, -
, -
, 20
, -
, -
, 5
For Non-Throttled
Client Map
Descriptors the
Scan_Interval
determines the
update rate.