Server Side Connection Descriptions; Server Side Node Descriptors - FieldServer Profibus DP FS-8700-20 Driver Manual

Fieldserver technologies computer driver instruction manual
Table of Contents

Advertisement

FS-8700-20 Profibus DP Driver Manual
5.3.

Server Side Connection Descriptions

The adapter used for the Profibus driver must be declared in the connections section.
Section Title
Connections
Column Title
Adapter
Protocol
Profibus_DP_Baud
Example
//
Client Side Connections
Connections
Adapter,
Prof_DP,
5.4.

Server Side Node Descriptors

Section Title
Nodes
Column Title
Node_Name
Node_ID
Protocol
Adapter
Example
Client Side Nodes
//
Nodes
Node_Name,
PDP_01,
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
Function
Adapter Name
Specify protocol used
Specifies network baudrate
Protocol,
Profibus_DP,
Function
Provide name for node
Station ID of the Slave
Specify protocol used
Specify
which
adapter
connected to the FieldServer
Node_ID,
1,
Legal Values
Prof_DP
Profibus_DP
9600, 19200, 93.75K, 187.5K,
500K, 750K, 1.5M, 3M, 6M,
12M
Profibus_DP_Baud
19200
Legal Values
Up
to
characters
0-125
Must be same as Value used for
System_Station_Address
Profibus_DP
is
Prof_DP
Protocol,
Profibus_DP,
Page 14 of 22
32
alphanumeric
Adapter
Prof_DP

Advertisement

Table of Contents
loading

Table of Contents

Save PDF