FS-8700-24 ControlNet Driver Manual
4.3.2.
Column Title
Node_Name
Block_Number
PCCC_Type
Address
Length
Note the number of bytes per PCCC_Type:
SINT, INT = 2 bytes, REAL, FLOAT = 4 bytes, BOOL, BIT, FLAG = 8 bits per byte
Each PLC file is 2000 bytes long and therefore the address values will range from zero
to a maximum value as indicated. The start address is specified in increments of the
basic data type specified under PCCC_Type.
The message buffers in the ControlNet card are each 498 bytes long and only one
message buffer can be allocated to a Map Descriptor. The Map Descriptor lengths are
therefore limited to maximum values as indicated when taking the data type byte lengths
into account.
4.3.3.
Column Title
Scan_Interval
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Driver Specific Map Descriptor Parameters

Function
Name of Node to
communicate with
PLC File Number
Type of PCCC data to be
transferred over
ControlNet
Starting address within file
Length of Map Descriptor

Timing Parameters

Function
Rate at which data is polled
Page 9 of 12
Legal Values
One of the node names
specified in "Node Descriptor"
above
For local node 7-39
For remote node 1-999
UINT, (SINT, INT) (REAL,
FLOAT) (BOOL, BIT, FLAG)
Equal types are shown in
brackets.
0 – 999 ( INT, SINT )
0 – 499 ( REAL, FLOAT )
0 – 15999 ( BOOL, BIT, FLAG )
1 – 249 ( INT, SINT )
1 – 124 ( REAL, FLOAT )
1 – 3984 ( BOOL, BIT, FLAG )
Legal Values
>0.1s