Driver Related Map Descriptor Parameters - FieldServer Optomux FS-8700-17 Driver Manual

Fieldserver technologies computer driver instruction manual
Table of Contents

Advertisement

FS-8700-17_Opto22.doc Manual

5.3.2 Driver Related Map Descriptor Parameters

Column Title
Function
Node_Name
Name of Node to fetch data from
Length of Map Descriptor. Commands and queries that use the value of
this Map Descriptor parameter are indicated in Appendix B.1 The driver
uses a maximum of 16 elements of data.
Length
The FieldServer kernel uses this parameter to ensure that no more than
one Client Map Descriptor has control of a range of array data
elements. It is therefore recommended that the parameter is set even
if not required by the command/query.- in these cases set it to 1.
This parameter is specified using one of the functions listed in Appendix
B.1. The parameter must be spelled and spaced exactly as provided in
Opto22_Function
the table. Leading and trailing spaces are not important but inter-word
spaces are very important. Tabs are not permitted.
This field is only required if the address/length method of module
Address*
position specification is used. Refer to Appendix A.2
This parameter only has meaning when the function is a read of digital
data. The parameter instructs the driver to unpack this data into
Opto22_Format*
separate bit states, writing each module position's state to a
consecutive Data Array element. Refer to Appendix A.2
An optional parameter used in conjunction with the Da_Byte_Name
Opto22_Trigger*
parameter. If the parameter is set, a poll will only be sent when the
trigger value is set. More information is provided in Appendix A.1.4.
Some Opto22_Functions require one or more additional arguments.
Opto22_modifier1*
SET TIME DELAY
GENERATE N PULSES
Opto22_modifier2*
READ AND AVERAGE INPUTS
This parameter allows the user to statically specify the positions (1-16)
of a module that will be affected by a command. When this parameter
Opto22_Mask*
is used and its value is non zero then the driver does not consider the
data contained in the position defining array even if it is also defined.
Refer also to Appendix A.1.1
This parameter is only required for dynamic module position
specification. The Data Array is used to tell the driver which module
Da_Bit_Name*
positions to affect by a command. Additional information is provided in
Appendix A.1.3
This driver uses DA_Byte_Name exclusively as a location for the
commands to trigger Map Descriptors and in which to store poll
Da_Byte_Name*
response status. Refer to Appendix A.1.4
One data element is used per Map Descriptor. The element is
determined by the Data_Array_Offset parameter.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Page 7 of 24
Legal Values
One
of
the
Node
names
specified
in
Section 5.2
1 - 1000
See Appendix
B.1
1..16
Bit, Packed
No, Yes
See
Appendix
B.1
0-65535
or
0x0000 – 0xffff
One of the Data
Array
names
from Section 4.
One of the Data
Array
names
from Section 4.

Advertisement