Replacement Of W7210Axxx With W7220A1000 (Jade Tm ) - Honeywell Design and Application Technical Reference Manual

Design and application guide for economizer controls
Table of Contents

Advertisement

Replacement of W7210Axxx with W7220A1000 (JADE
Step by step guide to assist you in successful replacement of the W7210 economizer with a
W7220 JADE
economizer controller:
TM
1. Remove all wires from the W7210. Mark each wire with the terminal designation (e.g.,
1,2,3,4, TR1, TR etc.) as it is removed from the W7210.
2. Mount JADE
on the inside of the Rooftop unit where it will be easy to read the display and
TM
to change the settings.
3. Wire JADE
to the existing M7215 motor using three new wires and ¼ in quick connects on
TM
motor end of wires:
M7215 wire termination
TR
TR1
IN (+)
4. Terminate wires removed from the W7210 to the JADE
W7210 wire termination
1
2
3
4
5
TR
TR1
P-P1
T-T1
So-So+
Sr-Sr+
+
-
24 VAC HOT
* Sensor to be changed
W7220 Wire termination
ACT 24V (hot)
ACT COM
ACT (2-10V)
W7220 wire termination
Y1-In
Y1-Out
Y2-In
Y2-Out
NA
R
C
NA
MAT*
OAT or S-Bus*
S-Bus*
ACT (2-10V)
ACT COM
ACT 24V