Honeywell Design and Application Technical Reference Manual page 124

Design and application guide for economizer controls
Table of Contents

Advertisement

Section 11 - W7220 JADE™ Economizer Module
Menu
Parameter
SET-
ENTH CURVE
POINTS
DCV SET
MIN POS
VENTMAX
VENTMIN
ERV OAT SP
EXH1 SET
63-8594-02 Honeywell Economizers
Table 3. Menu Structure (cont'd.)
Param-
Parameter
eter
Range and
Default
increments
Value
ES3
ES1, ES2,
ES3, ES4, or
ES5
1100pp
500 to 2000
m
ppm
increment by
100
2.8 V
2 to 10 Vdc
2.8 V
2 to 10 Vdc
or 100 to
9990 cfm
increment by
10
2.25 V
2 to 10 Vdc
or 100 to
9990 cfm
increment by
10
32ºF
0 to 50 ºF;
increment by
1
50%
0 to 100%;
increment by
1
118
Notes
Enthalpy boundary "curves" for economizing
using single enthalpy. See "" on page 19 and
Product Data sheet form 63-2700 for description
of enthalpy curves.
Displays ONLY if a CO2 sensor is connected.
Setpoint for Demand Control Ventilation of space.
Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space
ppm level below the setpoint.
Displays ONLY if a CO2 sensor is NOT
connected. With 2-speed fan units MIN POS L
(low speed fan) and MIN POS H (high speed fan)
settings are required. Default for MIN POS L is
3.2V and MIN POS H is 2.8V
Displays only if a CO2 sensor is connected. Used
for Vbz (ventilation max cfm) setpoint. Displays 2
to 10 V if <3 sensors (RA,OA and MA). In AUTO
mode dampers controlled by CFM With 2-speed
fan units VENTMAX L (low speed fan) and
VENTMAX H (high speed fan) settings are
required. Default for VENTMAX L is 3.2V and
VENTMAX H is 2.8V
Displays only if CO2 sensor is connected. Used
for Va (ventilation min cfm) setpoint. Displays 2 to
10 V if <3 sensors (RA,OA and MA). Va is only set
if DCV is used. This is the ventilation for less than
maximum occupancy of the space. In AUTO
mode dampers controlled by CFM With 2-speed
fan units VENTMIN L (low speed fan) and
VENTMIN H (high speed fan) settings are
required. Default for VENTMIN L is 2.5V and
VENTMIN H is 2.25V
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust
fan 1 is powered by the economizer. With 2-speed
fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1
L is 65% and Exh1 H is 50%