DUAL CENTRIFUGAL CHILLERS CONTROL APPLICATION

FUNCTIONAL DESCRIPTION
MORNING LEAD
CHILLER SELECTOR
78
1 = CHILLER 1 LEADS
2 = CHILLER 2 LEADS
3 = ALTERNATES
12
TOWER
19
CONTROL
4
ON
13
91
ENABLED
4
DISABLED
OFF
14
85
Item No.
Function
1
Indicates when chilled water is required by
fan system.
2
Chilled water pump ON-OFF-AUTO
function. In AUTO pump runs when system
needs chilled water.
3
Chiller ON-OFF-AUTO function (In ON and
AUTO chilled water flow required for chiller
to run).
4
Condenser pumps status. Pumps started by
chiller controls when chiller needed.
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
CHILLED WATER SETPOINT
42
1
MINIMUM
9
CHILLER 1
1
3
15
ON
AUTO
BY REMOTE
OPERATING
STATUS
CONTROLS
MODE
OFF
AUTO
CHILLER 2
Fig. 14. Dual Centrifugal Chiller Control Graphic.
6
46
50
MAXIMUM
CURRENT
7
CHILLER
CONTROL
SETPOINTS
SEQUENCES
42
5
17
11
78
NORMAL
100
PERCENT LOAD
ALARM
8
STATUS
MAX
CURRENT
100
00
NORMAL
55
5
5,6
Chiller leaving water temperature and setpoint.
7
Icon to select chilled water setpoint reset
dynamic sequence display (Fig. 15).
8
BMCS commandable load limiting functions.
9
Lead chiller selector function.
10-17
Operator information.
18
Control program coordinates chiller staging
and control.
19
Icon to select cooling tower control displays.
20
Icon to select chilled water flow and pressure
control displays.
309