Figure 8 shows how dynamic data can assist an operator.
This display provides the operator/engineer with the actual
operating values, at that instant, embedded in the sequence of
operations and allows the operator to adjust setpoints and review
AHU 3 DISCHARGE AIR STATIC PRESSURE CONTROL
PROGRAM: IF
STATIC PRESSURE SETPOINT
IF
4
PRESSURE SETPOINT
Fig. 8 Operator Graphic with Dynamic Data embedded in the Text Sequence.
MAXIMUM
INCHES
2.0
SETPOINT
2
OR LESS VAV BOXES ARE FULL OPEN, DECREMENT THE
INCHES EVERY
0.2
OR MORE VAV BOXES ARE FULL OPEN, INCREMENT THE STATIC
INCHES EVERY
0.2
169
INDOOR AIR QUALITY FUNDAMENTALS
results in real time. This is one of many operator displays that
can be designed to facilitate operator understanding and control
of IAQ.
MINUTES.
2.0
MINUTES.
2.0
ENGINEERING MANUAL OF AUTOMATION CONTROL
M10483