CONDITION FOR SUCCESSFUL OPERATION
The water must be supplied at a reasonably constant pressure.
LIMITATIONS
Modulating water flow through a constant air volume chilled
water coil usually causes a rise in space RH because the coil
leaving water temperature rises significantly.
SPECIFICATIONS
The flow of chilled water through the cooling coil shall be
controlled by a three-way valve modulated by a space
temperature PI control loop. The valve shall close to the coil
upon fan shutdown and open to the coil upon loss of actuator
motive force.
PSYCHROMETRIC ASPECTS
The temperature, and often moisture content, of leaving air
increases as the sensible cooling load lightens.
In the following chart it is assumed that:
1. Desired space and RA condition is 78°F DB and 50%
RH (65°F WB).
2. Design OA temperature is 95°F DB and 75°F WB.
3. Air entering the system is from the ECONOMIZER
CYCLE DECISION application. This system operates
on 35 percent OA during the cooling cycle.
4. Coil discharge temperature is 55°F.

TWO-POSITION CONTROL OF DIRECT EXPANSION COIL SYSTEM

Functional Description
TEMPERATURE CONTROL
DIFFERENTIAL (DEGREES)
7
2.5
3
76
76
2
COMPRESSOR
(MINUTES)
MINIMUM
MINIMUM
ON TIME
OFF TIME
8
10
8
AIR HANDLING SYSTEM CONTROL APPLICATIONS
SA 55°F DB
The following results are obtained:
Item
No.
Explanation
1
Mixed air temperature at cooling design
condition.
2
Air entering the coil is cooled along a line of
constant moisture content until saturation is
approached. Near saturation the moisture
content is reduced as the air is cooled. This
process involves both latent and sensible
cooling.
NOTE: Condition of coil leaving air will change with the
cooling load in the space. As the cooling load
decreases, the three-way valve will provide less chilled
water flow to the coil and the discharge air temperature
will rise (approximately along Line 2).
RELAY
COMPRESSOR
VOLTAGE MONITOR
CONTROL
PROGRAM
9
RELAY
5
4
OPEN
MA
SUPPLY
FAN
237
ENGINEERING CMANUAL OF AUTOMATION CONTROL
OA 95°F DB,
1
2
75°F WB
MA
RA 78°F DB,
50% RH
TO COMPRESSOR
START CIRCUIT
6
SA
1
ON
M10470
C2558-2