Table 5. Properties of Saturated Steam (continued).
Boiling
Point or
Steam
Gage
Temp-
Pressure,
erature
psig
Deg F
200
387.8
225
397.4
250
406.0
275
414.2
300
421.8
350
435.6
400
448.1
450
459.5
500
470.0
550
479.7
600
488.8
650
497.3
700
505.4
800
520.3
900
533.9
1000
546.3
ENGINEERING MANUAL OF AUTOMATIC CONTROL
Specific
Maximum
V
Volume
(For
Allowable
(V),
valve
Pressure
cu. ft/lb
sizing)
Drop, psi.
2.134
1.461
107.4
1.918
1.385
119.8
1.742
1.320
132.4
1.595
1.263
145.0
1.472
1.213
157.4
1.272
1.128
182.4
1.120
1.058
207.4
0.998
0.999
232.4
0.900
0.949
257.4
0.818
0.904
282.4
0.749
0.865
307.4
0.690
0.831
332.4
0.639
0.799
357.4
0.554
0.744
407.4
0.488
0.699
457.4
0.435
0.659
507.4