Voltage Conversion - Honeywell AUTOMATIC CONTROL Engineering Manual

For commercial buildings
Table of Contents

Advertisement

Full
Minimum Size of
Copper Wire, AWG
Load
Current
75C
Rating of
60C
RHW,
Motor
TW,
THW,
Amperes
UF
THWN
1
14
14
2
14
14
3
14
14
4
14
14
5
14
14
6
14
14
7
14
14
8
14
14
9
14
14
10
14
14
11
14
14
12
14
14
13
12
12
14
12
12
15
12
12
16
12
12
17
10
10
18
10
10
19
10
10
20
10
10
22
10
10
24
10
10
26
8
8
28
8
8
32
8
8
34
6
8
44
6
6
45
4
6
56
4
4
57
3
4
68
3
4
69
2
3
76
2
3
77
1
3
80
1
3
NOTES: 1. Single-phase all types with No Code letters.
All single-phase and polyphase squirrel-cage and synchronous motors with full voltage, resistor, or reactor starting,
no code letters or code letters F to V.
2. Squirrel-cage and synchronous motors:
With full voltage, resistor, or reactor starting, code letters b to e.
With autotransformer starting, not more than 30a with no code letters or more than 30a with code letters F to v.
High reactance squirrel-cage, not more than 30A, no code letters.
3. Squirrel-cage and synchronous motors with autotransformer starting more than 30A, no code letters. High
reactance squirrel-cage more than 30A, code letters B to E.
4. Squirrel-cage and synchronous motors with full voltage, resistor, or reactor starting or autotransformer starting with
more than 30A, code letter A. wound rotor, no code letter.

VOLTAGE CONVERSION

Existing Voltage
EMS Effective
Average
Peak
Peak-to-Peak
Table 26. Conductor Sizes and Overcurrent Protection for Motors.
Running
Maximum Allowable Rating or Setting (in Amperes) of Branch-Circuit,
Protection
of Motors.
Maximum
Setting of
Adjustable
90C
Protective
RHH,
Devices
THHN
Fuses
14
1.25
15
14
2.50
15
14
3.75
15
14
5.0
15
14
6.25
15
14
7.50
20
14
8.75
25
14
10.00
25
14
11.25
30
14
12.50
30
14
13.75
35
14
15.00
40
12
16.25
40
12
17.50
45
12
18.75
45
12
20.00
50
10
21.25
60
10
22.50
60
10
23.75
60
10
25.00
60
10
27.50
70
10
30.00
80
8
32.50
80
8
35.00
90
8
40.00
100
8
42.50
110
8
55.00
150
6
56.25
150
6
70.00
175
6
71.25
175
4
85.00
225
4
86.25
225
4
95.00
250
3
96.25
250
3
100.00
250
Table 27. Voltage Conversion Multipliers.
EMS Effective
1.110
0.707
0.354
Short-Circuit, and Ground-Fault Protective Devices
Note 1
ß
Inverse
Inverse
Time
Time
Circuit
Circuit
Breaker
Fuses
Breaker Fuses
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
15
20
20
20
25
25
20
25
25
20
30
30
25
30
30
25
35
35
30
35
35
30
40
40
30
40
40
35
45
45
35
45
45
40
50
50
40
50
50
40
60
60
45
60
60
50
70
70
60
70
70
60
80
80
70
90
90
70
110
110
90
125
125
90
150
150
125
150
150
125
175
175
150
175
175
150
200
200
175
200
200
175
200
200
175
Desired Voltage
Average
0.900
0.637
0.318
487
ENGINEERING MANUAL OF AUTOMATIC CONTROL
GENERAL ENGINEERING DATA
Note 3
Inverse
Time
Circuit
Breaker
Fuses
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
15
20
20
15
20
20
15
25
25
20
25
25
20
30
30
20
30
30
25
30
30
25
35
35
25
35
35
30
40
40
30
40
40
30
40
40
30
45
45
35
50
50
40
60
60
40
60
60
45
70
70
50
70
70
60
90
90
70
90
90
70
125
125
90
125
125
90
150
150
110
150
150
110
175
175
125
175
175
125
175
175
125
Peak
Peak-to-Peak
1.414
2.828
1.570
3.141
2.000
0.500
Note 4
Inverse
Time
Circuit
Breaker
15
15
15
15
15
15
15
15
15
15
20
20
20
25
25
25
30
30
30
30
35
40
40
45
50
60
70
70
90
90
110
110
125
125
125