Hitachi WJ200 Series Quick Reference Manual page 70

Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
Pulse train input/output
C047
scale conversion
PID FBV output
C052
high limit
PID FBV output
C053
low limit
Over-torque/under-torque
C054
selection
Over/under-torque level
C055
(Forward powering mode)
Over/under-torque level
C056
(Reverse regen. mode)
Over/under-torque level
C057
(Reverse powering mode)
Over/under-torque level
C058
(Forward regen. mode)
Signal output mode of
C059
Over/under-torque
Electronic thermal warning
C061
level
Zero speed detection level
C063
Heat sink overheat warning
C064
Communication speed
C071
Modbus address
C072
Communication parity
C074
Communication stop bit
C075
"C" Function
Description
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in × (C047)
Set range is 0.01 to 99.99
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0
to 100%
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
Two option codes:
00...Over-torque
01...Under-torque
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Two option codes:
00...During accel., decel. and
constant speed
01...During constant speed only
Set range is 0 to 100%
Setting 0 means disabled.
Set range is 0.0 to 100.0Hz
Set range is 0 to 110 °C
Eight option codes:
03...2,400 bps
04...4,800 bps
05...9,600 bps
06...19,200 bps
07...38,400 bps
08...57,600 bps
09...76,800 bps
10...115,200 bps
Set the address of the inverter on
the network. Range is 1 to 247
Three option codes:
00...No parity
01...Even parity
02...Odd parity
Two option codes:
1...1 bit
2...2 bit
68
Run
Defaults
Mode
Lnitial data
Units
Edit
1.00
100.0
0.0
00
100.
100.
100.
100.
01
90
0.00
100.
05
baud
1.
00
1
%
%
-
%
%
%
%
-
%
Hz
°C
bit