Func.
Name
Code
Communication error
C076
select
Communication error
C077
time-out
Communication wait time
C078
O input span calibration
C081
OI input span calibration
C082
Thermistor input (PTC)
C085
span calibration
Debug mode enable *
C091
Communication selection
C096
EzCOM start adr. of master
C098
EzCOM end adr. of master
C099
EzCOM starting trigger
C100
Up/Down memory mode
C101
selection
"C" Function
Description
Selects inverter response to
communications error.
Five options:
00...Trip
01...Decelerate to a stop and trip
02...Disable
03...Free run stop (coasting)
04...Decelerates to a stop
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec
0.0 = disabled
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
Scale factor between the external
frequency command on terminals
L–OI (voltage input) and the
frequency output,
range is 0.0 to 200%
Scale factor of PTC input.
Range is 0.0 to 200%
Displays debug parameters.
Two option codes:
00...Disable
01...Enable <Do not set>
(for factory use)
00...Modbus-RTU
01... EzCOM
02... EzCOM<administrator>
01-08
01-08
00... Input terminal
01... Always
Controls speed setpoint for the
inverter after power cycle.
Two option codes:
00...Clear last frequency (return to
default frequency F001)
01...Keep last frequency adjusted
by UP/DWN
69
Run
Defaults
Mode
Lnitial data
Units
Edit
02
0.00
sec.
0.
msec.
100.0
100.0
100.0
00
00
01
01
00
00
%
%
%