Hitachi L700 SERIES Instruction Manual page 249

L700 series
Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

Code
Function name
b034
Run/power-on warning time
b035
Rotational direction restriction
b036
Reduced voltage start selection
b037
Function code display restriction
b038
Initial-screen selection
Automatic user-parameter setting
b039
function enable
b040
Torque limit selection
Torque limit (1)
b041
(forward-driving in 4-quadrant mode)
Torque limit (2)
b042
(reverse-regenerating in 4-quadrant
mode)
Torque limit (3)
b043
(reverse-driving in 4-quadrant mode)
Torque limit (4)
b044
(forward-regenerating in 4-quadrant
mode)
b045
Torque limit LADSTOP enable
b046
Reverse Run protection enable
Controller deceleration and stop on
b050
power loss
DC bus voltage trigger level during
b051
power loss
Over-voltage threshold during power
b052
loss
Deceleration time setting during power
b053
loss
Initial output frequency decrease
b054
during power loss
Proportional gain setting for nonstop
b055
operation at power loss
Integral time setting for nonstop
b056
operation at power loss
Maximum-limit level of window
b060
comparators O
Minimum-limit level of window
b061
comparators O
Hysteresis width of window
b062
comparators O
Maximum-limit level of window
b063
comparators OI
Minimum-limit level of window
b064
comparators OI
Hysteresis width of window
b065
comparators OI
Maximum-limit level of window
b066
comparators OI
Minimum-limit level of window
b067
comparators O/OI/O2
Hysteresis width of window
b068
comparators O/OI/O2
b070
Operation level at O disconnection
b071
Operation level at OI disconnection
b072
Operation level at O2 disconnection
(Note)<>indicate the setting range of 90 to 160kW
Monitored data or setting
0. to 9999. (0 to 99990), 1000 to 6553 (100000 to 655300) (hr)
00 (enabling both forward and reverse rotations),
01 (enabling only forward rotation), 02 (enabling only reverse rotation)
0 (minimum reduced voltage start time) to 255 (maximum reduced
voltage start time)
00 (full display), 01 (function-specific display), 02 (user setting),
03 (data comparison display), 04 (basic display)
00 (screen displayed when the STR key was pressed last), 01 (d001),
02 (d002), 03 (d003), 04 (d007), 05 (F001)
00 (disabling), 01 (enabling)
00 (quadrant-specific setting), 01 (switching by terminal),
02 (analog input), 03 (option 1), 04 (option 2)
0. to 150. (%), no (disabling torque limitation)
0. to 150. (%), no (disabling torque limitation)
0. to 150. (%), no (disabling torque limitation)
0. to 150. (%), no (disabling torque limitation)
00 (disabling), 01 (enabling)
00 (disabling), 01 (enabling)
00 (disabling), 01 (nonstop deceleration to stop),
02 (DC voltage constant control, with resume), 03 ( without resume)
0.0 to 999.9, 1000. (V)
0.0 to 999.9, 1000. (V)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.00 to 10.00 (Hz)
0.00 to 2.55
0.000 to 9.999 /10.00 to 65.53 (s)
0. to 100. (lower limit : b061 + b062 *2) (%)
0. to 100. (lower limit : b060 - b062 * 2) (%)
0. to 10. (lower limit : b061 - b062 / 2) (%)
0. to 100. (lower limit : b064 + b066 *2) (%)
0. to 100. (lower limit : b063 - b066 *2) (%)
0. to 10. (lower limit : b063 - b064 / 2) (%)
-100. to 100. (lower limit : b067 + b068* 2) (%)
-100. to 100. (lower limit : b066 - b068 * 2) (%)
0. to 10. (lower limit : b066 - b067 / 2) (%)
0. to 100. (%) or "no" (ignore)
0. to 100. (%) or "no" (ignore)
-100. to 100. (%) or "no" (ignore)
8 - 7
Chapter 8 List of Data Settings
Setting
Default
during
operation
(allowed or
_FF
0.
00
6
04
01
00
00
120.
120.
120.
120.
00
01
00
220.0/
440.0
360.0/
720.0
1.00
0.00
0.20
0.100
100
0
0
100
0
0
100
-100
0
no
no
no
Change
during
operation
Page
(allowed or
not)
not)
4-66
4-7
4-43
4-79
4-81
4-82
4-93
4-95
4-94
4-84
4-74