8.4 Extended Function Mode

Code
Function name
A001
Frequency source setting
A002
Run command source setting
A003
Base frequency setting
Base frequency setting,
A203
2nd motor
Base frequency setting,
A303
3rd motor
A004
Maximum frequency setting
A204
Maximum frequency setting, 2nd motor 30. to 400. (Hz)
A304
Maximum frequency setting, 3rd motor
A005
[AT] selection
A006
[O2] selection
A011
[O]-[L] input active range start frequency 0.00 to 99.99, 100.0 to 400.0 (Hz)
A012
[O]-[L] input active range end frequency 0.00 to 99.99, 100.0 to 400.0 (Hz)
A013
[O]-[L] input active range start voltage
A014
[O]-[L] input active range end voltage
[O]-[L] input active range start frequency
A015
selection
A016
External frequency filter time const.
A017
Easy sequence function selection
A019
Multispeed operation selection
A020
Multispeed frequency setting
A220
Multispeed frequency setting, 2nd motor 0.0 or "start frequency" to "maximum frequency, 2nd motor" (Hz)
A320
Multispeed frequency setting, 3rd motor 0.0 or "start frequency" to "maximum frequency, 3rd motor" (Hz)
A021
Multispeed 1 setting
A022
Multispeed 2 setting
A023
Multispeed 3 setting
A024
Multispeed 4 setting
A025
Multispeed 5 setting
A026
Multispeed 6 setting
A027
Multispeed 7 setting
A028
Multispeed 8 setting
A029
Multispeed 9 setting
A030
Multispeed 10 setting
A031
Multispeed 11 setting
A032
Multispeed 12 setting
A033
Multispeed 13 setting
A034
Multispeed 14 setting
A035
Multispeed 15 setting
A038
Jog frequency setting
A039
Jog stop mode
*1 This setting is valid only when the OPE-SR is connected.
Monitored data or setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block),
02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2),
06 (pulse-string input), 07 (easy sequence), 10 (operation function result)
01 (control circuit terminal block), 02 (digital operator), 03 (RS485),
04 (option 1), 05 (option 2)
30. to "maximum frequency " (Hz)
30. to "maximum frequency, 2nd motor" (Hz)
30. to "maximum frequency, 3rd motor" (Hz)
30. to 400. (Hz)
30. to 400. (Hz)
00 (switching between O and OI terminals),
01 (switching between O and O2 terminals),
02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1),
04 (switching between O2 and keypad potentiometer) (*1)
00 (single),
01 (auxiliary frequency input via O and OI terminals) (nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible),
03 (disabling O2 terminal)
0. to "[O]-[L] input active range end voltage" (%)
"[O]-[L] input active range start voltage" to 100. (%)
00 (external start frequency), 01 (0 Hz)
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
00 (disabling), 01 (enabling)
00 (binary: 16 speeds selectable with 4 terminals),
01 (bit: 8 speeds selectable with 7 terminals)
0.0 or "start frequency" to "maximum frequency" (Hz)
0.0 or "start frequency" to "1st maximum frequency" (Hz)
0.0 or "start frequency" to "2nd maximum frequency" (Hz)
0.0 or "start frequency" to "3rd maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
"Start frequency" to 9.99 (Hz)
00 (free-running after jogging stops [disabled during operation]),
01 (deceleration and stop after jogging stops [disabled during operation]),
02 (DC braking after jogging stops [disabled during operation]),
03 (free-running after jogging stops [enabled during operation]),
04 (deceleration and stop after jogging stops [enabled during operation]),
05 (DC braking after jogging stops [enabled during operation])
8 - 3
Chapter 8 List of Data Settings
Default
operation
_FF
02
02
60.
60.
60.
60.
60.
60.
00
03
0.00
0.00
0.
100.
01
31.
00
00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.00
00
Setting
Change
during
during
operation
Page
(allowed
(allowed
or not)
or not)
4-8
4-8
4-11
4-11
4-12
4-14
4-15
4-96
4-47
4-50