Hitachi L700 SERIES Instruction Manual page 201

L700 series
Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

Register
Function name
No.
142Ah
Frequency arrival setting for accel.
142Bh
142Ch
Frequency arrival setting for decel.
142Dh
142Eh PID deviation level setting
142Fh Frequency arrival setting for
1430h
acceleration (2)
1431h Frequency arrival setting for
deceleration (2)
1432h
1433h to
(Reserved)
1437h
1438h Maximum PID feedback data
1439h Minimum PID feedback data
143Ah (Reserved)
Over-torque (forward-driving) level
143Bh
setting
Over-torque (reverse regenerating)
143Ch
level setting
Over-torque (reverse driving) level
143Dh
setting
Over-torque (forward regenerating)
143Eh
level setting
143Fh (Reserved)
1440h (Reserved)
Electronic thermal warning level
1441h
setting
1442h Alarm code output
1443h Zero speed detection level
1444h Heat sink overheat warning level
1445h to
(Reserved)
144Ah
144Bh Communication speed selection
144Ch Node allocation
Communication data length
144Dh
selection
144Eh Communication parity selection
144Fh Communication stop bit selection
Selection of the operation after
1450h
communication error
1451h Communication timeout limit
1452h Communication wait time
1453h Communication mode selection
1454h (Reserved)
1455h [O] input span calibration
1456h [OI] input span calibration
1457h [O2] input span calibration
1458h (Reserved)
1459h Thermistor input tuning
145Ah to
(Reserved)
145Eh
145Fh Debug mode enable
1460h to
(Reserved)
1468h
1469h Up/Down memory mode selection
146Ah Reset mode selection
146Bh Restart mode after reset
146Ch (Reserved)
146Dh FM gain adjustment
146Eh AM gain adjustment
146Fh AMI gain adjustment
Chapter 4 Explanation of Functions
Function code
R/W
Monitoring and setting items Data resolution
C042 (high)
R/W
0 to 40000
C042 (low)
R/W
C043 (high)
R/W
0 to 40000
C043 (low)
R/W
C044
R/W 0 to 1000
C045 (high)
R/W
0 to 40000
C045 (low)
R/W
C046 (high)
R/W
0 to 40000
C046 (low)
R/W
-
-
Inaccessible
C052
R/W 0 to 1000
C053
R/W 0 to 1000
R/W
C055
R/W 0 to 150
C056
R/W 0 to 150
C057
R/W 0 to 150
C058
R/W 0 to 150
-
-
Inaccessible
-
-
Inaccessible
C061
R/W 0 to 100
C062
R/W 0 (disabling alarm output), 1 (3 bits), 2 (4 bits)
C063
R/W 0 to 10000
C064
R/W 0 to 200
-
-
Inaccessible
2 (loopback test), 3 (2,400 bps), 4 (4,800 bps), 5
C071
R/W
(9,600 bps), 6 (19,200 bps)
C072
R/W 1. to 32.
C073
R/W 7 (7 bits), 8 (8 bits)
C074
R/W 00 (no parity), 01 (even parity), 02 (odd parity)
C075
R/W 1 (1 bit), 2 (2 bits)
0 (tripping), 1 (tripping after decelerating and
stopping the motor), 2 (ignoring errors), 3
C076
R/W
(stopping the motor after free-running), 4
(decelerating and stopping the motor)
C077
R/W 0 to 9999
C078
R/W 0 to 1000
C079
R/W 0 (ASCII), 1 (Modbus-RTU)
-
-
Inaccessible
C081
R/W 0 to 65530
C082
R/W 0 to 65530
C083
R/W 0 to 65530
-
-
Inaccessible
C085
R/W 0 to 10000
-
-
Inaccessible
C091
R
0/1
-
-
Inaccessible
0 (not storing the frequency data), 1 (storing the
C101
R/W
frequency data)
0 (resetting the trip when RS is on), 1 (resetting
the trip when RS is off), 2 (enabling resetting only
C102
R/W
upon tripping [resetting when RS is on]),
3(resetting only trip)
0 (starting with 0 Hz), 1 (starting with matching
C103
R/W
frequency), 2 (restarting with active matching
frequency)
-
-
Inaccessible
C105
R/W 50 to 200
C106
R/W 50 to 200
C107
R/W 50 to 200
4 - 139
Register
No.
0.01 [Hz]
0.01 [Hz]
0.1 [%]
0.01 [Hz]
0.01 [Hz]
-
0.1 [%]
0.1 [%]
-
1 [%]
1 [%]
1 [%]
1 [%]
-
-
1 [%]
-
0.01 [Hz]
1 [ ]
-
-
-
-
-
-
-
0.01 [sec.]
1 [msec.]
-
-
1
1
1
-
0.1
-
-
-
-
-
-
-
1 [%]
1 [%]
1 [%]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents