First alarm: 002-03
15.4
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
 Outputs programmed for heavy smoke / heat alarm are
23
activated.
 Each heavy smoke / heat alarm is presented with a "title",
i.e. "Heavy smoke" or "Heavy heat" will be added to the
normal fire alarm information:
Heavy smoke
Zone
002-03
User definable alarm text for 002-03.
Menu
The printer (if available) will print each heavy smoke / heat
alarm, e.g.:
** Heavy Smoke **
Zone 002 Address 03
SMOKE
YYYY-MM-DD hh:mm
User definable alarm text
(if progr.)
Heavy smoke / heat alarm will be reset when the fire alarm
respectively is reset, see chapter "Alarm reset", page 49.

Alert Annunciation alarm (AA alarm)

When the AA function is enabled, indicated by the LED Routing
equipment "Fire brigade tx delay" (L14), the indications, print-outs,
actions etc. are the same as for a normal fire alarm (see above) except
for the c.i.e. output for routing equipment (fire brigade tx), which
will not be activated directly. There will also be a "title", i.e. "Alert
annunciation" or "Alert annunciation acknowledged" will be added to
the normal fire alarm information.
acknowledged within an acknowledge time and reset within an
investigation time, otherwise the output(s) for routing equipment (fire
23
General heavy smoke / heat alarm and individual alarm points / zones.
44
Alarm number 1 (of 1)
Address
SMOKE
1 zone in alarm
The AA alarm has to be