Panasonic MEW01349 Operating Instructions Manual page 43

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
First alarm: 002-03
Latest alarm: 003-11
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
More than one alarm point activating fire alarm.
Example; fire alarm in zone 002, address 03 (within zone 002) and
nine other fire alarms (of which the latest alarm is 003-11) in four
different zones:
Zone
002-03
User definable alarm text for 002-03.
Menu
Next zone
"
" after the presentation number is automatically added
SMOKE
depending on the type of alarm point (i.e. SMOKE, HEAT, MULTI or
MCP).
User definable alarm text For each alarm point can an individual
alarm text be shown (if programmed) or the default control unit alarm
text (if programmed). For each zone it is an individual alarm text (if
programmed). Up to 40 alphanumeric characters can be used.
Additional information
First alarm, Latest alarm, Alarm number and number of zones in
alarm.
LEDs "Alarms queued" (L6) blinking (0.4 / 0.4 sec.) are indicating
that more than one fire alarm is activated. To scroll through the
alarms, use the push button "Alarms queued" (P8).
The fire alarms are stored in a circular buffer and when scrolling from
the last to the first alarm, the LEDs "Alarms queued" will be turned
off for three seconds.
Next zone. Use the soft key "
zones in alarm.
When scrolling through the zones, the first alarm point activated in the
next zone will be shown. The "
only if there are alarms in more than one zone.
The first alarm will be automatically displayed again, 20 seconds after
the latest time the "Alarms queued" or "
used.
41
Alarm number 1 (of 10)
Address
SMOKE
4 zones in alarm
" (P5)to scroll through the
Next zone
" button will be available
Next zone
" buttons where
Next zone