Display Current Consumption In Unit (H5/A4) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
28.5
Action
Text in display
"Menu"
"↵ "
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
Scroll to menu A4
A4 Display current consumption in unit
Select control unit: : 00 (press ↵)
"↵ "
"↵ "
Wait......
No reply from control unit.....
Current consumption in control unit 00:
Low capacity voltage diff: xxxxx mV
"↵ " or "ESC"
A4 Display current consumption in unit
Rev: -
Display current consumption in unit
(H5/A4)
The resolution is not very high, i.e. the displayed values give only a
rough idea of the current consumption.
Control unit: The total current consumption (including the charging
current at 24V) for the selected control unit (c.i.e.) when it is
connected to the mains (230 V AC), i.e. this function is not working
by battery backup.
Charging: The battery charging current for the selected control unit
(c.i.e.). This is at 24 V, i.e. before the DC/DC converter for battery
charging voltage etc.
From rectifier: xxxx mA
Charging: xxxx mA (battery temperature xx°C)
58
During the battery capacity check the voltage is measured with and
without a resistor. A difference between these two voltages > 700 mV will
result in a "Low battery capacity" fault.
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
58
121
Comments
According to chapter
"Access code for service /
maintenance (H5 and
H8)", see page 116.
Write control unit number
and press "↵ "
If the control unit don't
exist or don't answer.
Scroll to another menu or
press "ESC".