Gas Pipe Capacities; Horizontal Venting - Two Pipes; Specific Gravity Conversion Factors - Modine Manufacturing PSH Installation And Service Manual

Separated combustion high efficiency gas-fired unit heaters
Table of Contents

Advertisement

INSTALLATION
Horizontal Two Pipe Venting
Figure 9

Horizontal Venting - Two Pipes

1. When horizontal vents pass through a combustible wall (up
to 8 inches thick), the vent passage must be constructed
and insulated as shown in Figure 10.
2. The termination of horizontally vented system must extend
12 inches beyond the exterior surface of an exterior wall.
3. The combustion air pipe must be a minimum of 16 inches
below the vent pipe, and 24 inches from the exterior wall.
4. Support the vent and combustion air pipe as shown in
Figure 10.
Figure 10
Exhaust Vent Construction Through Combustible Walls
and Support Bracket
METAL
SLEEVE
2" MIN.
VENT PIPE
DIAMETER
METAL FACE
PLATE
METAL
SLEEVE
2" MIN.
1"
Piping
CAUTION
Gas pressure to unit heater controls must never exceed 14"
W.C. (1/2 psi).
When leak testing the gas supply piping system, the appliance
and its combination gas control must be isolated during any
pressure testing in excess of 14" W.C. (1/2 psi).
The appliance should be isolated from the gas supply piping
system by closing its field installed manual shut-off valve.
1. Installation of piping must be in accordance with local
codes, and ANSI Z223.1, "National Fuel Gas Code," or
CAN/CGA-B149 in Canada.
2. Piping to units should conform with local and national
requirements for type and volume and gas handled, and
pressure drop allowed in the line. Refer to Table 5, to
determine the cubic feet per hour (cfh) for the type of gas
FIBER GLASS
INSULATION
MIN. 2"
1"
9"
VENT TERMINATION
45
SUPPORT BRACKET
9"
(where required)
(Make from 1" x 1" steel angle)
Table 2

Gas Pipe Capacities

In Cu. Ft. per Hour with Pressure Drop of 0.3 in W.C. with Specific Gravity 0.60.
Length
Diameter of Pipe — Inches
of Pipe
in Ft.
1/2
3/4
15
76
218
30
73
152
45
44
124
60
50
105
75
97
90
88
105
80
120
150
180
210
240
270
300
450
600
Length
Diameter of Pipe — Inches
of Pipe
in Ft.
2
3
15
2480
6500
30
1650
4700
45
1475
3900
60
1150
3250
75
1120
3000
90
930
2600
105
920
2450
120
860
2300
150
710
2000
180
720
1950
210
660
1780
240
620
1680
270
580
1580
300
545
1490
450
450
1230
600
380
1030
and size of unit to be installed. Using this cfh value and the
length of pipe necessary, determine the pipe diameter from
Table 2. Where several units are served by the same main,
the total capacity, cfh, and length of main must be
considered. Avoid pipe sizes smaller than 1/2". Table 2
allows for the usual number of fittings with a 0.3; W.C.
pressure drop. Where the gas supplied has a specific
gravity other than 0.60, apply the multiplying factor as given
in Table 3.
3. After threading and reaming the ends, inspect piping and
remove loose dirt and chips.
4. Support piping so that no strains are imposed on unit or
controls.
5. Use two wrenches when connecting piping to unit controls.
Table 3

Specific Gravity Conversion Factors

Multiplying factors to be used with Table 1 when the specific gravity of gas is
other than 0.60.
Natural Gas
Specific
Gravity
Factor
0.55
1.04
0.60
1.00
0.65
0.962
Heater Parts from ACF Greenhouses
1
1-1/4
1-1/2
440
750
1220
285
590
890
260
435
700
190
400
610
200
345
545
160
320
490
168
285
450
158
270
420
120
242
380
128
225
350
205
320
190
300
178
285
170
270
140
226
119
192
4
6
8
12880
38700
79000
9700
27370
55850
7900
23350
45600
6800
19330
39500
6000
17310
35300
5400
15800
32250
5100
14620
29650
4800
15680
27920
4100
12240
25000
4000
11160
22800
3700
10330
21100
3490
9600
19740
3250
9000
18610
3000
8500
17660
2500
7000
14420
2130
6000
12480
Propane Gas
Specific
Gravity
Factor
1.50
0.633
1.53
0.626
1.60
0.612
7

Advertisement

Table of Contents
loading

Table of Contents