Meter-Timing Gas; Dials Of Typical Gas Meter - Modine Manufacturing PSH Installation And Service Manual

Separated combustion high efficiency gas-fired unit heaters
Table of Contents

Advertisement

CHECKING INPUT RATE
Table 4
Time for 1
Input, Cu. Ft. per Hour, When Meter Dial Size is:
Revolution,
Sec.
1/2 cu. ft.
10
180
12
150
14
129
16
112
18
100
20
90
22
82
24
75
26
69
28
64
30
60
35
51
40
45
45
40
50
36
55
33
60
30
70
26
80
22
90
20
100
18
120
15

Meter-Timing Gas

(Time required for one revolution is charted for various size
meter dials and various rates of gas input in cu. ft. per hour. To
convert to Btuh, multiply by the heating value of the gas used.)
Figure 10

Dials of Typical Gas Meter

(B) Pressure Method
The pressure method determines input by measuring the
pressure of the gas in the manifold in inches of water.
1. Determine correct manifold pressure from Table 5.
2. Remove access panel (see Figure 11a) and locate
combination gas control.
3. Move gas control knob (or lever) to off.
4. Remove the 1/8" pipe plug in outlet pressure tap in
combination gas control (see Figure 11b) and attach water
manometer or "U" tube which is at least 12" high.
5. Follow lighting instructions and turn thermostat up to get
unit to fire.
CAUTION
Check the gas inlet pressure at the unit upstream of the
combination gas control. The inlet pressure should be 6"-7"
W.C. on natural gas or 11"-14" W.C. on propane. If inlet pressure
is too high, install and additional pressure regulator upstream of
the combination gas control.
Important —Inlet pressure and manifold pressure must be
checked with unit in operation when making final adjustments.
12
1 cu. ft.
2 cu. ft.
5 cu. ft.
360
720
1800
300
600
1500
257
514
1286
225
450
1125
200
400
1000
180
360
900
164
327
818
150
300
750
138
277
692
129
257
643
120
240
600
103
206
514
90
180
450
80
160
400
72
144
360
65
131
327
60
120
300
51
103
257
45
90
225
40
80
200
36
72
180
30
60
150
6. If pressure as indicated by "U" tube is less than 1/2" higher
or lower than indicated in TAble 5, adjust regulator as
described under "meter-Timing method," Step 3.
If pressure as indicated by "U" tube is more than 1/2"
higher or lower than indicated in Table 5, check inlet
pressure at unit. The inlet pressure should be 6"-7" W.C.
pressure on natural gas and 11"-14" W.C. on propane gas.
After adjustment move gas control knob (or level) to off and
replace 1/8" pipe plug. With plug in place move knob (or leave)
to on.) Replace the access panel, making use a good tight seal
is achieved around the entire perimeter of the access panel.
Figure 11a
VENTING
LABEL
LIGHTING
INSTRUCTION &
RATING PLATE
COMBUSTION AIR
INLET COLLAR
Figure 11b
IGNITION
MANIFOLD
CONTROL
PILOT
TUBING
IGNITION
MAIN BURNER
CABLE
Heater Parts from ACF Greenhouses
POWER EXHAUSTER
PRESSURE
SWITCH
JUNCTION
BOX
FAN GUARD
FAN MOTOR
SIGHT GLASS
GAS SUPPLY
CONNECTION
(Not Shown)
ACCESS PANEL
COMBINATION
GAS CONTROL
MANIFOLD
PRESSURE REGULATOR
PRESSURE TAP
ADJUSTMENT SCREW
(UNDER CAP SCREW)