Appendix B: MS-9200
Configuration
The control panel needs to be programmed to either "Points" or "Zones",
depending on which type of address is to be annunciated.
LDM Address Switches (SW1 & SW2) must be set to address '01', '02', '03'
or '04'. The CPU will differentiate between the addresses.
• For Zones use address 01 (56 zones).
• For Points use addresses 01, 02, 03 and 04 (198 points).
Note: Do not omit any address when annunciating 198 points or the MS-9200 will indicate
a constant trouble.
Alarm Only Annunciation of Zones
The table below illustrates the configuration of the LDM Series modules to
annunciate the alarm state of all 56 software zones (no zone troubles), and two
NACs, with the first eight points of address '01' dedicated to the MS-9200
system function LEDs (see Figure 29 below).
LDM Module
Address '01'
LDM-32F
LDM-E32F
Alarm Only Annunciation of Zones - With 8-Point Shift
The table below illustrates the configuration of the LDM Series modules to
annunciate the alarm state of all 56 software zones (no zone troubles), and two
NACs, with the last eight points of address '01' dedicated to the MS-9200
system function LEDs (see Figure 29 below).
LDM Module
Address '01'
LDM-32F
LDM-E32F
System Alarm
J5
Figure 29 System Functions to Output Connectors - 1
42
LDM Output Connectors
J5
Sys Funct
Z1 to Z8
Z25 to Z32
Z33 to Z40
Table 11 Alarm Only Setup
LDM Output Connectors
J5
Z1 to Z8
Z9 to Z16
Z33 to Z40
Z41 to Z48
Table 12 Alarm Only Setup with Shift
Not Used
J6
J7
Z9 to Z16
Z41 to Z48
J6
J7
Z17 to Z24
Z49 to Z56
System Alarm
J8
LDM-32F PN 50055:C 03/20/01
Configuration
J8
Z17 to Z24
Z49 to Z56
J8
Z25 to Z32
Sys Funct
Not Used