Configuration; Setting Rotary Switches - Fire-Lite LDM-32F Instruction Manual

Lamp driver module
Table of Contents

Advertisement

Appendix C: MS-9600

Configuration

Setting Rotary Switches

LDM Address Switches (SW1 & SW2) must be set to an address. Use the
following table to set these switches.
Note: Do not omit any address when annunciating 636 points or the MS-9600 will indicate
a constant trouble.
M = Module
FACP
Address
13 - 19
Note: If a UDACT-F is installed and selected in control panel programming, it will
automatically assign addresses 20 - 31 to the UDACT-F and disable the selection of
these addresses.
52
D = Detector
SW1
SW2
1
0
1
2
0
2
3
0
3
4
0
4
5
0
5
6
0
6
7
0
7
8
0
8
9
0
9
10
1
0
11
1
1
12
1
2
20
2
0
21
2
1
22
2
2
23
2
3
24
2
4
25
2
5
26
2
6
27
2
7
28
2
8
29
2
9
30
3
0
31
3
1
Table 23 SW1 & SW2 Switch Settings
Relay Activation for:
8 System Points & Zones 1-56
Zones 57-99 & 2 NACs
Loop 1, Address M1 - M64
Loop 2, Address M1 - M64
Loop 1, Address M65 - M128
Loop 2, Address M65 - M128
Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159
Loop 1, Address D1 - D64
Loop 2, Address D1 - D64
Loop 1, Address D65 - D128
Loop 2, Address D65 - D128
Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159
Not Used
8 System Points & Zones 1-56
Zones 57-99 & 2 NACs
Loop 1, Address M1 - M64
Loop 2, Address M1 - M64
Loop 1, Address M65 - M128
Loop 2, Address M65 - M128
Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159
Loop 1, Address D1 - D64
Loop 2, Address D1 - D64
Loop 1, Address D65 - D128
Loop 2, Address D65 - D128
Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159
Configuration
LDM-32F PN 50055:C 03/20/01