Wiring for Lamp/LED
Wiring for Lamp/LED
• All LEDs must be located in the same room as the LDM modules.
• For 5 volt output use a 680 ohm, 1/4-watt resistors for each point if
using 2 mA LEDs.
• For 24 volt output use a 10K ohm, 1/4-watt resistors for each point if
using 2 mA LEDs.
• LEDs: use red for alarm points, yellow for trouble points and green
for output points.
• Use the cables supplied in the cable kit to wire connectors on LDM.
The figure below illustrates LEDs being powered by the 5 volt output from
LDM-32F, J11 pin 1.
Resistor
J5
Figure 14 Typical LDM-to-Graphics Display Connection @ 5VDC
The figure below illustrates LEDs being powered by the 24 volt output from
LDM-32F, J9 pin 3.
Resistor
J5
Figure 15 Typical LDM-to-Graphics Display Connection @ 24VDC
LDM-32F PN 50055:C 03/20/01
Custom Graphic Display
Point Status LEDs
J6
J7
J11
LDM-32F
Custom Graphic Display
Point Status LEDs
J6
J7
J11
LDM-32F
J8
J10
LAMP
J9
POWER
J8
J10
LAMP
J9
POWER
2. Installation
Wiring is not
supervised
System
Trouble
LED
Wiring is not
supervised
System
Trouble
LED