Lamp/LED Driver Operation

Lamp/LED Driver Operation
LDM Address Switches (SW1 & SW2) must be set to address '01'.
Lamp Driver outputs do not latch - they track or follow the status of each zone/
point that they are assigned to annunciate. The table below defines the ON
status of each lamp driver output.
Note: Control Switches marked 'Not Used' will still function as local LAMP TEST or local
ACKNOWLEDGE switches for their respective points.
Note: If Alarm Only mode is selected, column labeled Yellow LED is not applicable and
control switches do not function.
CPU Points
Annunciator
Point #1
Annunciator
Point #2
Annunciator
Point #3
Annunciator
Point #4
Annunciator
Point #5
Annunciator
Point #6
Annunciator
Point #7
Annunciator
Point #8
1. If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight Sensiscan 2000 CPU
functions (ACK, SIL, RESET, LAMP TEST, NAC1, NAC2, MUNTIE, RELAY) will be
shifted from annunciator points 1 through 8 (as shown above) to points 57 through 64
(provided those points exist in the system and the LDM-32F is set to address 01).
2. Optional control switches are active only if all of these conditions are met:
a) '8-Point Shift' (DIP switch #4) is set to OFF.
b) Receive Only (DIP Switch #5) is set to OFF.
c) Switch Inhibit (DIP Switch #7) is set to OFF.
3. Use green LEDs to indicate activation on controlled output circuits.
Table 4 Annunciator Point Assignment to LDMs
LDM-32F PN 50055:C 03/20/01
Alarm
1
(Red LED)
System Alarm
Not Used
Not Used
Not Used
NAC #1 Activated
NAC #2 Activated
Remote Signaling
of Municipal Tie
3
Activated
Alarm Relay
3
Activated
Appendix A: Sensiscan 2000
Trouble/Supv
(Yellow LED)
System Trouble
Signal Silence
Not Used
Supervisory
Condition
Trouble Status of
3
Circuit
Trouble Status of
3
Circuit
Trouble Status of
Circuit
Module Trouble,
Power Failure, or
Disabled Circuit
2
Control Switches
Acknowledge
Signal Silence
System Reset
Not Used
NAC #1
NAC #2
Remote Signaling
of Municipal Tie
Alarm Relay
35