Configuration

Alarm Only Annunciation of Points

The tables below illustrate the configuration of the LDM Series modules to
annunciate the alarm state of all 99 points (detectors or modules) with the first
eight points of address '01' dedicated to the MS-9200 system functions (see
Figure 29 on page 42).

Detectors

Set address '01' and '02' for detectors.
LDM Module
Address '01'
LDM-32F
LDM-E32F
LDM Module
Address '02'
LDM-32F
LDM-E32F

Modules

Set address '03' and '04' for modules.
LDM Module
Address '03'
LDM-32F
LDM-E32F
LDM Module
Address '04'
LDM-32F
LDM-E32F
LDM-32F PN 50055:C 03/20/01
LDM Output Connectors
J5
Sys Funct
25 to 32
LDM Output Connectors
J5
57 to 64
89 to 96
Table 15 Alarm Only Setup - Detectors
LDM Output Connectors
J5
1 to 8
33 to 40
LDM Output Connectors
J5
65 to 72
97 to 99
Table 16 Alarm Only Setup - Modules
Appendix B: MS-9200
J6
J7
1 to 8
9 to 16
33 to 40
41 to 48
J6
J7
65 to 72
73 to 80
97 to 99
Not Used
J6
J7
9 to 16
17 to 24
41 to 48
49 to 56
J6
J7
73 to 80
81 to 88
Not Used
Not Used
J8
17 to 24
49 to 56
J8
81 to 88
Not Used
J8
25 to 32
57 to 64
J8
89 to 96
Not Used
45