Alarm/Trouble Annunciation Of Zones; Alarm/Trouble Annunciation Of Zones - With 8-Point Shift - Fire-Lite LDM-32F Instruction Manual

Lamp driver module
Table of Contents

Advertisement

Configuration

Alarm/Trouble Annunciation of Zones

The table below (also see Figure 30 on page 44) illustrates the configuration
of the LDM Series modules to annunciate the alarm and trouble states for all
56 software zones with the first eight points of address '01' dedicated to the
MS-9200 system functions (see Figure 31 on page 44).
LDM Module
Address '01'
LDM-32F
1st LDM-E32F
2nd LDM-E32F
3rd LDM-E32F
Alarm/Trouble Annunciation of Zones -
With 8-Point Shift
The table below (also see Figure 30 on page 44) illustrates the configuration
of the LDM Series modules to annunciate the alarm and trouble states for all
56 software zones with the last eight points of address '01' dedicated to the MS-
9200 system functions as listed below (see Figure 32 on page 44).
LDM Module
Address '01'
LDM-32F
1st LDM-E32F
2nd LDM-E32F
3rd LDM-E32F
LDM-32F PN 50055:C 03/20/01
J5
System Functions
Z9 to Z12
Z25 to Z28
Z41 to Z44
Table 13 Alarm/Trouble Setup
J5
Z1 to Z4
Z17 to Z20
Z33 to Z36
Z49 to Z52
Table 14 Alarm/Trouble Setup with Shift
Appendix B: MS-9200
LDM Output Connectors
J6
J7
Z1 to Z4
Z13 to Z16
Z17 to Z20
Z29 to Z32
Z33 to Z36
Z45 to Z48
Z49 to Z52
LDM Output Connectors
J6
J7
Z5 to Z8
Z9 to Z12
Z21 to Z24
Z25 to Z28
Z37 to Z40
Z41 to Z44
Z53 to Z56
System Functions
J8
Z5 to Z8
Z21 to Z24
Z37 to Z40
Z53 to Z56
J8
Z13 to Z16
Z29 to Z32
Z45 to Z48
43