Exploded View Of Duct Smoke Detector Components; General Description; Contents Of Duct Smoke Detector Kit; Detector Installation - Honeywell Gamewell-FCI MS-95 Manual

Table of Contents

Advertisement

[2] figure 1. exPLoded VieW of ducT Smoke deTecTor comPonenTS:
METAL
SAMPLING TUBE
(sold seperately)

[3] generaL deScriPTion

Smoke introduced into an air duct system will be distributed throughout the
entire building. Smoke detectors designed for use in air duct systems are used
to sense the presence of smoke in the duct.
Model D4120 and D4S Duct Smoke Detectors utilize 4-wire photoelectric tech-
nology for the detection of smoke. This detection method, when combined
with an efficient housing, samples air passing through the duct allowing de-
tection of a developing hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated and appropriate action can be taken to shut off
fans, blowers, change over air handling systems, etc. These actions can fa-
cilitate the management of toxic smoke and fire gases throughout the areas
served by the duct system.
The D4120 and D4P120 detectors are designed to operate on 24 VDC/VAC or
120 VAC. Alarm and supervisory relay contacts are available for control panel
interface (alarm initiation), HVAC control, and other auxiliary functions. Aux-
iliary relays are provided for fan shut down. Detector interconnection provides
signaling of up to 50 other detectors in the loop for multiple fan shut down.
These detectors are not designed for 2-wire applications.
[3.1] deTecTor feaTure SeT
-Utilizes 2D51 plug-in head
-2 sensors to 1 power board capability
-Cover missing signal
-Sampling tubes install from front or rear of detector
-Compatible with existing accessories
[4] conTenTS of The ducT Smoke deTecTor kiT
1.
Sensor/power board assembly and cover(s)
2.
Three #10 sheet metal screws for mounting
3.
One test magnet
4.
Drilling template
5.
One sampling tube end cap
6.
One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must
be the correct length for the width of the duct where it will be installed.
See Table 1 on page 3 to determine the inlet tube required for different duct
widths.

[5] deTecTor inSTaLLaTion

[5.1] VerifY air fLoW direcTion and VeLociTY
Model D4120 detectors are designed to be used in air handling systems with
air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12
feet can be accommodated. Be sure to check engineering specifications to
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.
SS-300-000
EXHAUST TUBE
SENSOR HEAD
MAGNET TEST LOCATION
POWER BOARD
POWER BOARD MODULE COVER
SENSOR MODULE
[5.2] deTermine mounTing LocaTion and configuraTion
On ducts wider than 18 inches it is recommended that the detector be
mounted downstream of a bend, obstruction in the duct, or the supply or
return air inlet.
Exception: Installation of duct detectors can be on or within a commercial
packaged rooftop heating and air-conditioning system, fire/smoke dampers
and economizers. They may be mounted in either the supply and/or return air
section as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted
in a side-by-side "rectangular" configuration or a top-over-bottom "square"
configuration as shown in Figure 2. If mounting in the square configuration,
remove the rear attachment screw, rotate the unit at the hinge, and replace the
screw into the new attachment hole as shown in Figure 2. Do NOT remove
the hinge screw during this process. Final installation approval shall be based
upon passing section 7.2.2 and/or 8.2.4 tests.
figure 2:
REMOVE SCREW AND PIVOT
DETECTOR AS SHOWN BELOW.
[5.3] driLL The mounTing hoLeS
Remove the paper backing from the mounting template supplied. Affix the
template to the duct at the desired mounting location. Make sure the template
lies flat and smooth on the duct.
[5.3.1] for recTanguLar Side-bY-Side mounTing configuraTion:
Center punch at (4) target centers: (2) "A" for sampling tubes and (2) "B" for
the rectangular configuration mounting tabs as shown on mounting template.
Drill pilot holes at target "A" centers and cut two 1.375 inch diameter holes
using a 1
3
/
inch hole saw or punch. Drill .156 inch diameter holes using a
8
inch drill at target "B" centers.
2
4-WIRE
COVER
REPLACE SCREW
TO SECURE DETECTOR
IN PLACE.
I56-2967-002R
H0549-01
H0550-00
5
/
32

Advertisement

Table of Contents
loading

Table of Contents