Temperature Requirements - HP DL740 - ProLiant - 4 GB RAM User Manual

Hp proliant dl740 server user guide
Hide thumbs Also See for DL740 - ProLiant - 4 GB RAM:
Table of Contents

Advertisement

Installing the Server in a Rack

Temperature Requirements

To be sure of continued safe and reliable operation of the equipment, install the
system in a well-ventilated, climate-controlled environment.
The HP Maximum Recommended Ambient Operating Temperature (TMRA) for
most server products is 35° C (95° F). The temperature in the room where the rack is
located should not exceed 35° C (95° F).
The operating temperature inside the rack will always be higher than the room
temperature and is dependent on the configuration of equipment in the rack. The
TMRA for each piece of equipment should be checked before installation. The
maximum internal rack temperature for the configuration should not exceed the
values shown in Table 2-1.
Table 2-1: Rack Internal Temperature Maximums
Equipment Included
Rack-mountable ProLiant
DL740 servers
HP rack-mountable options
Other manufacturers' options
CAUTION: To reduce the risk of damage to the equipment when installing
third-party options:
2-8
Refer to other manufacturers'
Be sure that the optional equipment does not impede airflow to the
rack-mountable ProLiant DL740 servers or increase the internal rack
temperature beyond the HP specified maximum rating.
Be sure that the Manufacturer's TMRA for the optional equipment is not
exceeded when the equipment is installed in the rack.
Maximum Internal Rack
Temperature
35° C (95° F)
35° C (95° F)
specifications
HP ProLiant DL740 Server User Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Proliant dl740

Table of Contents