Choosing a Location
Choose a location that meets the following criteria.
Table 3
Location Criteria
Weight
Room
temperature
Power
source
Air quality
Humidity
Clearance
Chapter 1
23 kg (50 lbs)
10-35º C (50-95º F)
AC power voltage: 100-127 V or 200-240 V
Line frequency: 50-60 Hz
Note
Locate the AC outlet near the autoloader. The AC
power cord is this product's main AC disconnect
device and must be easily accessible at all times.
Minimal sources of particulate contamination. Avoid areas near
frequently used doors and walkways, stacks of supplies that collect
dust, and smoke-filled rooms.
Caution
Excessive dust and debris can damage tapes and
tape drives.
20-80% RH
Standalone configuration — includes the cosmetic enclosure and
feet (see
Installing a Standalone Autoloader in a Rack
page 20):
Back
56 cm (22 inches) for cooling and service.
Front
86 cm (34 inches) for operator access.
Rackmounted configuration (see
on page 22)
Above
Requires 6 EIA (26.67 cm or 10.5 inches) of
clearance in a rack.
Back
Allow adequate room for service access, at least 61
cm (24 inches).
Front
Requires 86 cm (34 inches) for tape access.
on
Rackmounting the Autoloader
Choosing a Location
19