THIS VENT SYSTEM HAS BEEN LISTED FOR USE WITH SPECIFIED
RHEEM, RUUD, WEATHERKING AND HEAT CONTROLLER OIL
FURNACES BY UL AND ULC. SEE FURNACE RATING PLATE FOR
VERIFICATION.

INSTALLATION INSTRUCTIONS

!
NOTE: FLUE GAS TEMPERATURES MUST NOT EXCEED
575
F AT VENT SYSTEM INLET.
o
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUST-
MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRI-
CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL
INJURY OR PROPERTY DAMAGE.
Copyright © 1995, Tjernlund Products, Inc. All rights reserved
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
MODEL SS1-R
Recognize this symbol as an indication of important Safety Information!
OWNER INSTRUCTIONS, DO NOT DESTROY
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
REV. 5/95
P/N 8504046

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SS1R SIDESHOT (DISCONTINUED VERSION-PRE UC1 UNIVERSAL CONTROL) 8504046 REV 0595 and is the answer not in the manual?

Questions and answers

Summary of Contents for TJERNLUND SS1R SIDESHOT (DISCONTINUED VERSION-PRE UC1 UNIVERSAL CONTROL) 8504046 REV 0595

  • Page 1: Installation Instructions

    MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRI- CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL INJURY OR PROPERTY DAMAGE. DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE. Copyright © 1995, Tjernlund Products, Inc. All rights reserved P/N 8504046...
  • Page 2: Table Of Contents

    Template A Vent Hood Terminus........................21 ® SideShot is a registered trademark of Tjernlund Products, Inc. for their Model SS1-R Vent System. DESCRIPTION The SS1-R is a mechanical vent system designed and listed for use with specified Rheem, Ruud, Weatherking and Heat Controller oil fired furnaces.
  • Page 3: Installation Restrictions

    GENERAL INFORMATION These units have been factory tested and rated in accordance with AMCA standard 210, Test Code for Air Moving Devices and also rated in accordance with the following Canadian Standards: CAN/CSA - B140.0-M87 General Requirements For Oil Burning Equipment;...
  • Page 4: Safety Inspection Of A Previously Used Appliance

    *SAFETY INSPECTION OF A PREVIOUSLY INSTALLED OIL APPLIANCE (Perform prior to SS1-R installation) The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition for continuing use. This procedure is based on central furnace installations and it should be recognized that generalized procedures cannot anticipate all situations.
  • Page 5: Vent Hood Termination Clearances For U.s. Installations

    VENT HOOD TERMINATION CLEARANCES FOR U.S. INSTALLATIONS Install the SS1-R according to the requirements of the National Fire Protection Association #31, #54 and #211 as follows, (See Diagram A): • The exit terminals of mechanical draft systems shall not be less than 7 feet above grade when located adjacent to public walk ways.
  • Page 6: Vent Hood Termination Clearances For Canadian Installations

    TERMINATION CLEARANCES FOR CANADIAN INSTALLATIONS The SS1-R has been CSA Listed according to the requirements of “Mechanical Flue-Gas Exhausters” CSA Std B255-M81 and the “Installation code for Oil burning Equipment” CSA Std B139-M91. (See Diagram. A1) • A venting system shall not terminate underneath a veranda, porch, or deck, or above a paved sidewalk or a paved driveway that is located between two buildings, and that serves both buildings.
  • Page 7: Installation

    INSTALLATION Tools required: • Reciprocating Saw • 1/2", 7/16",5/8" Wrench • Drill and 1/8", 1/4", 1/2" Bits, 1” hole saw • 1/4" Masonry Drill Bit • Blade Screwdriver • 1/4", 5/16”, 11/32" Nut Driver or Socket • Wire Cutter/Stripper • Hammer •...
  • Page 8: Installation Of Rain Shield

    DIAGRAM D OUTERMOST CASING INNER FLANGE OF VENT 8. Slide the Vent Hood through the wall while taking care installing the rain shield as shown, (See Diagram E). The nuts located on the Vent Hood outermost casing should be facing up when sliding it through the wall. Mount Vent Hood to the exterior using four #8 x 3"...
  • Page 9: Plenum Installation

    NOTCH BRACING It is recommended and local codes may dictate that the joist be reinforced as outlined below. Bracing of the rim joist is not necessary. 1. Cut two 2 x 4 pieces of wood 28 inches in length. 2. Center both pieces on each side of the floor joist above the notch and drive 8 16D or larger nails into each piece, (See Diag. H) DIAGRAM H CONNECTING THE PLENUM TO THE VENT HOOD NOTES: Cut any nails which are protruding downward from the subfloor that may come in contact with the SS1-R.
  • Page 10: Installation Of Vent Pipe

    5. Connect the other end of wall support bracket to the stud on the plenum using the supplied 1/4"-20 keps nut. (See Diagram J). DIAGRAM J INSTALLATION OF VENT PIPE Single wall vent pipe is not allowed in unconditioned or unheated space. When Installing the SS1-R vent system, a barometric draft damper control must be used.
  • Page 11 4. Using a tube cutter, cut the sensing tube 2" from the elbow directed at the vent pipe inlet collar, (See Diagram L). Discard the cut off section of metal tube. DIAGRAM L DIAGRAM M 5. Attach the vent pipe inlet collar to the rear inlet port making sure that the sensing tube is orientated as shown, (See Diagram M). NOTE: Alignment marks on the inlet collar and plenum casing must match.
  • Page 12: Electrical Wiring

    ELECTRICAL WIRING OF SS1-R ON OIL EQUIPMENT All wiring from the SS1-R to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermedi- ate metal conduit, rigid non-metallic conduit, electrical metallic tubing, Type MI Cable, Type MC Cable, or be otherwise suitably protected from physical damage.
  • Page 13: Field Wiring Connections

    FIELD WIRING CONNECTIONS (DIAGRAM Q) Disconnect power supply when wiring SS1-R failure to do so may result in personal injury and/or equipment damage. DIAGRAM Q NOTE: All wiring connections are to be made with wire nuts inside oil burner junction box. 1.
  • Page 14: Installation Of R1 Relay And Junction Box Extension

    INSTALLATION OF R1 RELAY AND JUNCTION BOX EXTENSION (DIAGRAM R) 1. Install the junction box extension only after the wiring has been completed. 2. Rotate the junction box extension so that the R1 relay locates to the front. (toward the cabinet door) 3.
  • Page 15: Combustion Air

    DRAFT ADJUSTMENT OIL The SS1-R Vent system will properly vent a wide range of BTU/hr. input capacities. To compensate for different burner capacities, vent connector lengths and wind conditions it features a draft adjustment located on the outside of the Vent Hood. In general, positioning the draft adjustment inward will cause the SS1-R to operate at lowest capacity.
  • Page 16: System Operation Check Out

    Accessory air intakes are available that connect to the burner motor, using it to pull in the outdoor air. The Tjernlund IN-FORCER Combustion Air Intake tempers the raw outdoor air as it is delivered to the burner.
  • Page 17: Troubleshooting Electrical Problems

    Extreme caution must be exercised to prevent injury. If you are unable to determine the defective part with the use of this guide, call your Tjernlund distributor or Tjernlund Products direct at 1-800-255- 4208 for further assistance. SYMPTOM 1: SS1-R MOTOR WILL NOT OPERATE Step 1.
  • Page 18 SYMPTOM 3: APPLIANCE WILL NOT OPERATE, BUT SS1-R DOES Step1. Set draft adjustment according to "Draft Verify draft adjustment has been made. Adjustment Procedure" on Page14. Step 2. SS1-R and appliance are not interlocked With the appliance calling for heat and SS1-R correctly or malfunction of appliance controls.
  • Page 19: Maintenance

    MAINTENANCE DIAGRAM U WHEEL INSPECTION (DIAGRAM U) 1. The SS1-R blower wheel must be inspected annually. Particulates, such as soot, oil impurities and sheet rock dust, can prevent proper venting and will cause noise and vibration. Follow instructions, below for motor/wheel assembly removal. 2.
  • Page 20: Warranty

    Tjernlund Products, Inc. will issue credit or provide a free part to replace one that becomes defective during the two year warranty period. If the part is over 30 months old, proof of date of the installation in the form of the contractor sales/installation receipt is necessary to prove the unit has been in service for under two years.